PairGain HiGain-2 HRU-612 Manual Download Page 11

Section 150-612-102

Revision 03

Page 11

TABLE 2.  HRU-612 Test Procedures.

Step

Action

1

Depress the loopback LB button on the HRU front panel for at least 5 seconds.

2

Verify that the GREEN  HRU front panel loopback LB NET LED turns on, indicating that the HRU  is in
its (NREM) loopback state.  Also verify, if  possible, that the HLU displays the message ”NREM” also
indicating that the HRU is in loopback (see Figure 5).

3

Have the C.O. tester  transmit a T1 test signal into the HLU and measure that the returned (looped)
signal is error free.

4

If the above test fails, remove the HRU from its loopback state by again depressing the HRU loopback
button for 5 seconds.  Verify that the loopback NET LED is off.

5

Have the C.O. tester send the HLU (4 in 7) in-band loop-up (NLOC) for 5 seconds.  Verify that the HLU
displays the message “ NLOC”  indicating that the HLU unit is in its network loopback state.

6

Repeat step  3.  If the test passes, the problem is in the cable pair or the HRU.  If it fails, the problem is
in the C.O.

7

To verify that the proper ports are use for the VHDSL & DS1 pairs, use an ohm-meter to verify that the
VHDSL HRU-612 port has a 180 k T to R resistive signature in contrast to the DS1 ports which have a
15 ohm T to R resistive signature.

8

If the CPE 60 mA. switch option is set.  Verify that the external NID is under power and that the voltage
across its front panel “60 mA MON” test points measures between 55 and 65 mv.  This indicates that the
CPE current is between 55 & 65 mA.  Note that the external NID’s LOOP POWER option must be set to
its “THRU” position when powered by the HRU.

NOTE:  When T1 loopback tests are made on the HiGain-2 system with external metallic loopback connections
at either end, the DS1 code that exists at the metallic loopback interface may be different from the DS1 code
being received at the opposite end when the DS1 user option is set to AUTO.  For example, if the HRU has a
metallic loopback and the HLU’s receive pattern’s code is changed from AMI to B8ZS and then the all 0 pattern
is sent into the HLU, the HRU remains in its AMI mode and thus loops all 0’s.  This causes the HRU to indicate a
LOS condition which then causes the HLU to output the AIS pattern.

Summary of Contents for HiGain-2 HRU-612

Page 1: ...IONS 2 3 SPECIFICATIONS 3 4 CERTIFICATION 3 5 WARRANTY 4 6 TECHNICAL ASSISTANCE 4 B FUNCTIONAL DESCRIPTION 7 FUNCTIONAL OPERATION 4 8 FRONT PANEL 6 9 OPTIONS 7 10 LOOPBACKS 9 C INSTALLATION AND TEST 1...

Page 2: ...smart jack loopback Conforms to TR TSY 000312 Provisioning switches for CPE current RCV LBO and XMT LOS initiated loopback or AIS Front panel jacks for test access RS 232 front panel terminal access f...

Page 3: ...50 Celsius 5 to 95 non condensing Mounting Single width 400 type mechanics slot Dimensions 5 6 H x 1 4 W x 5 6 D 4 CERTIFICATION 4 01 FCC Compliance The HRU 612 List 2 has been tested and found to co...

Page 4: ...Technical Assistance is available 24 hours a day 7 days a week by contacting PairGain s Customer Service Engineering group at one of the following numbers Telephone 800 638 0031 714 832 9922 Fax 714 8...

Page 5: ...the screen displays The port is configured as DCE with 8 data bits 1 stop bit and no parity Striking the SPACE bar several times invokes autobaud from 1200 to 9600 baud Note that if the RS 232 port in...

Page 6: ...B NET GREEN LED indicating the HRU is in a loopback state in which the signal from the NETwork is being looped back to the NETwork CI YELLOW LED indicating the HRU is in a loopback state in which the...

Page 7: ...611 100 for more details The HRU also has three user options set by switches located at the back of the unit as shown in Figure 4 Each switch has two settings as follows refer to the block diagram in...

Page 8: ...en the HRU does not function as the NID but is connected to an external NID It allows the external NID to set the appropriate NI level 15 Configures the T1 RCV LEVEL to 15 dB This sets the T1 output s...

Page 9: ...t jack loopback state It remains in this state until a loopdown command is detected or the default time out period if enabled expires 10 04 When the HRU is in its AIS ENA smart jack metallic loop back...

Page 10: ...ed or unframed The loop down command for both is the standard 3 in 5 five second pattern C INSTALLATION AND TEST 11 INSTALLATION 11 01 Upon receipt of the equipment visually inspect it for signs of da...

Page 11: ...e C O 7 To verify that the proper ports are use for the VHDSL DS1 pairs use an ohm meter to verify that the VHDSL HRU 612 port has a 180 k T to R resistive signature in contrast to the DS1 ports which...

Page 12: ...ustomer at HRU 612 NREM Network Remote Loopback DSX signal is looped back to DSX at HRU SMJK Remote Smartjack Loopback Signal from DSX is looped back at HRU by the HRU smartjack module TLOS Transmit L...

Page 13: ...ng System Settings review mode defined above FRM Frame SF ESF UNFR NONE Defines the type of frame pattern being received from the DSX 1 Displayed during System Settings mode defined above CODE Line Co...

Page 14: ...tiated by 2 in 5 in band loopback code or out of band ESF data link code See Figure 5 NREM Network Remote Loopback Loopback at HRU remote towards network initiated from C O network by intelligent line...

Page 15: ...Hour ES Errored Seconds The number of 1 second intervals that contained at least 1 CRC error This value is a running total of the last 24 Hours VHDSL 24 Hour UAS Unavailable Seconds The number of sec...

Page 16: ...Section 150 612 102 Revision 03 Page 16 Figure 7 HRU 612 Maintenance Terminal Main Menu Figure 8 HRU 612 View Span Status Display...

Page 17: ...Section 150 612 102 Revision 03 Page 17 Figure 9 HRU 612 System Settings Menu Figure 10 HRU 612 Set Clock Menu...

Page 18: ...Section 150 612 102 Revision 03 Page 18 Figure 11 HRU 612 View Performance Data Display Figure 12 HRU 612 View Performance History Display...

Page 19: ...2 102 Revision 03 Page 19 Figure 13 HRU 612 View Alarm History Display Copyright 1996 PairGain Technologies Inc PairGain is a registered trademark CopperOptics and HiGain are trademarks of PairGain Te...

Reviews: