Page 1: ...Document in original language 269415 A001 Duct fan prio 315 400 AC EC Operation and Maintenance Instructions GB ...
Page 2: ...269415 A001 ...
Page 3: ... 1 General 3 3 2 Technical data 4 3 2 1 Dimension and weight 4 3 2 2 Performance 5 3 2 3 Wiring diagram 6 3 3 Transportation and storage 7 4 Installation 7 4 1 Commissioning 8 5 Maintenance 8 5 1 Important 8 5 2 Cleaning the fan 9 6 Troubleshooting 9 7 Deinstallation dismantling 9 8 Disposal 9 ...
Page 4: ......
Page 5: ... 1 Safety of machinery Electrical equipment of machines Part 1 General requirements EN 60335 1 Household and similar electrical appliances Safety Part 1 General requirements EN 60335 2 80 Household and similar electrical appliances Safety Part 2 80 Particular requirements for fans EN 50106 Safety of household and similar electrical appliances Particular rules for routine tests referring to applian...
Page 6: ...ries Caution Indicates a risk of damaging the product or prevent optimal operation Important This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Childr...
Page 7: ...o 315 400 AC EC are intended for transportation of air in air handling systems The fans are meant for use in ducted systems and should always be duct connected on the inlet side No moving parts shall be accessible after instal lation prio 315 400 AC EC are adapted to continuous operation Danger The fans are not to be used in hazardous environments or connected to flue ducts The appliance must be c...
Page 8: ...o 315 EC prio 400 EC AC Model øA øB øC D F Weight kg prio 315 EC 314 322 375 407 205 10 prio 400 EC AC 399 407 459 493 266 15 5 D øC øB øA 60 ø10 15 45 100 F 45 Fig 2 Dimension prio 315 AC prio 355 EC AC Model øA øB øC D F Weight kg prio 315 AC 313 407 459 676 357 15 5 prio 355 EC AC 353 407 459 632 335 18 5 269415 A001 ...
Page 9: ... 600 0 1000 2000 3000 4000 m h Q m s Ps Pa 19056 19059 5V 7 2V 10V prio 315 EC 2 5V 0 0 5 1 1 5 2 0 200 400 600 0 2000 4000 6000 m h Q m s Ps Pa 19218 19217 4 8 7V 10V prio 355 EC 2 4 0 0 5 1 1 5 2 0 200 400 600 0 2000 4000 6000 m h Q m s Ps Pa 18996 18995 4 9V 7 2V 10V prio 400 EC 2 4V 0 0 5 1 1 5 2 0 200 400 600 800 0 2000 4000 6000 m h Q m s Ps Pa 19075 19074 4 4V 6 8V 10V prio 400 EC 3 2 3V 26...
Page 10: ...GY BN BU BK YE GN TK TK N L C Fig 3 prio 315 400 RD YE BU WH BN WH WH BU BK YE GN 10V GND RSA RSB 0 10V COM NC N L Fig 4 prio 315 400 EC RD YE BU WH BN 10V GND RSA RSB 0 10V WH WH BK YE GN BK BK L3 L2 L1 COM NC Fig 5 prio 400 EC 3 RD Red GN Green YE Yellow BN Brown BU Blue BK Black WH White GY Gray 269415 A001 ...
Page 11: ... the mains power supply must be preceded by an all pole circuit breaker with a minimum 3 mm gap Do not lift the fans by the connecting cable connection box motor bracket impeller or inlet cone The fan can be installed in any direction mounting brackets pre mounted for easy installation Arrow on the fan casing indicates the direction of the airflow If damp air is transported in the duct the fan mus...
Page 12: ...ltage 6 10 according to IEC 38 Rated current must not be exceeded with more than 5 at rated voltage The direction of rotation should correspond to direction of rotation arrow 3 phase Smoothness of motor operation no abnormal noises Sound levels exceeding 70 dB A may occur depending on size see www pacificventilation com for detailed information 5 Maintenance 5 1 Important Danger Make sure that the...
Page 13: ...an im peller distorted Listen for abnormal operating noise 6 Troubleshooting The following applies in case the fan has stopped Try to restart the fan by cutting the power a couple of minutes Ensure that the impeller is not locked Disconnect the power supply remove any obstacles Check that the fan starts after reconnecting the current Should the fan not start please contact your place of purchase 7...
Page 14: ...269415 A001 ...
Page 15: ...269415 A001 ...
Page 16: ...ration and Maintenance Instructions 269415 en_GB 2021 05 12 A001 Pacific Ventilation Pty Ltd 2 63 Wells Rd Chelsea Heights VIC 3196 Australia Email info pacificventilation com Phone AU 1300 733 833 NZ 0800 100 326 ...