LMX SERIES® OPERATION MANUAL
SECTION 4: Technical Specifications
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 45 of 463
4.10.3
112LMX AC Input
The Model 112LMX single-phase input voltages, required input currents at full rated load
and recommended service input currents are stated as below.
NO
INPUT VOLTAGE
INPUT CURRENT
RECOMMENDED SERVICE
1
100 Vac ±10%, 47-63 Hz
21 Arms
25 A
2
110 Vac ±10%, 47-63 Hz
19 Arms
25 A
3
120 Vac ±10%, 47-63 Hz
18 Arms
25 A
4
200 Vac ±10%, 47-63 Hz
11 Arms
15 A
5
208 Vac ±10%, 47-63 Hz
11 Arms
15 A
6
220 Vac ±10%, 47-63 Hz
10 Arms
15 A
7
230 Vac ±10%, 47-63 Hz
9 Arms
15 A
8
240 Vac ±10%, 47-63 Hz
9 Arms
15 A
4.10.4
140LMX AC Input
The Model 140LMX single-phase input voltages, required input currents at full rated load
and recommended service input currents are stated as below.
NO
INPUT VOLTAGE
INPUT CURRENT RECOMMENDED SERVICE
1
208 Vac
∆
±10%, 47-63 Hz
23 Arms
40 A
2
220 Vac
∆
±10%, 47-63 Hz
22 Arms
40 A
3
230 Vac
∆
±10%, 47-63 Hz
21 Arms
40 A
4
240 Vac
∆
±10%, 47-63 Hz
20 Arms
40 A
5
220/380 Vac ±10%, 47-63 Hz
13 Arms
20 A
6
230/400 Vac ±10%, 47-63 Hz
12 Arms
20 A
7
240/416 Vac ±10%, 47-63 Hz
12 Arms
20 A
8
277/480 Vac ±10%, 47-63 Hz
11 Arms
20 A
4.10.5
160LMX AC Input
The Model 160LMX single-phase input voltages, required input currents at full rated load
and recommended service input currents are stated as below.
NO
INPUT VOLTAGE
INPUT CURRENT RECOMMENDED SERVICE
1
208 Vac
∆
±10%, 47-63 Hz
28 Arms
40 A
2
220 Vac
∆
±10%, 47-63 Hz
26 Arms
40 A
3
230 Vac
∆
±10%, 47-63 Hz
25 Arms
40 A
4
240 Vac
∆
±10%, 47-63 Hz
25 Arms
40 A
5
220/380 Vac ±10%, 47-63 Hz
15 Arms
20 A
6
230/400 Vac ±10%, 47-63 Hz
14 Arms
20 A
7
240/416 Vac ±10%, 47-63 Hz
14 Arms
20 A
8
277/480 Vac ±10%, 47-63 Hz
14 Arms
20 A
2
Cost Option
3
Cost Option