Pacific energy SPECTRUM Installation And Operating Instructions Manual Download Page 7

280514-24 

SUPER-SD1 7

22"

559mm

12"

305mm

18"

457mm

30"

762mm

25"

635mm

11"

279mm

11"

279mm

18"

457mm

4"

102mm

4"

102mm

16"

406mm

16"

406mm

28"

711mm

10"

254mm

20"

508mm

14"

357mm

26"

660mm

16"

406mm

18"

457mm

22"

559mm

28"

711mm

8"

203mm

8"

203mm

8"

203mm

5"

127mm

15"

381mm

Minimum

Clearance to 

Combustibles

Procedure:

CAUTION: THE STRUCTURAL INTEGRITY OF THE MO-
BILE HOME FLOOR, WALL AND CEILING/ROOF MUST 
BE MAINTAINED.

Note: See "Combustion Air" section on page 10.
1.  Position stove and fl oor protection with hole for combus-

tion air in accordance with the clearances as stated on 
the label and in Figure #1.

2.  Mark the position for the hole in the ceiling and roof by 

using a string and plumb-bob.

3.  Check that the intended location will not interfere with fl oor 

joists, ceiling joists or rafters before proceeding further.

4.  Cut a hole in the ceiling and roof to suit the chimney 

system and frame in the sides. The chimney support is 
mounted to the framing.

5.  Assemble chimney sections so the fi nished length is rest-

ing on the support and protruding through the roof. Avoid 
having joints between ceiling and roof.  Install radiation 
shield. Assemble fl ashing and storm collar and be sure to 
maintain the vapour barrier at this point. (Seal securely.) 
Attach rain cap and check fl ashing for leaks.

6.  Install connector as per manufacturer's instructions.
7.  Attach stove to fl ooring using two 1/4" x  2" or longer lag 

screws.

Mobile Home 
Installation

Warning:

 Under no circumstances is this heater to be installed 

in a makeshift or "temporary" manner. It may be fi red only 
after the following conditions have been met.

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE 

SERVING ANOTHER APPLIANCE.

DO NOT INSTALL IN A SLEEPING ROOM.

- Outside air supply must be used for Mobile Home installa-

tions see Figure #2, Page 8.

- The services of a competent or certifi ed installer, (certifi ed 
by the Wood Energy Technical Training program (WETT) - in 
Canada, Hearth Education Foundation (HEARTH) - in U.S.A.,) 
are strongly recommended.

Clearances

This heater must be installed with listed double-wall connector 
and compatible chimney system listed on page 7.
Clearances to combustible surfaces and materials are shown 
below in Figure #1 and Figure #1.
Clearances may be reduced with various heat insulating ma-
terials. Consult local fi re codes and authorities for approval.

NOTE:

 Longer chimney lengths and different pitch fl ashings 

may be used. All other parts listed must be installed (see 
Figure #2, Page 8). Install all components to the connector 
or chimney manufacturer's installation requirements. Consult 
your chimney supplier for installation advice.

FIG. #1

Double Wall Connector - Residential

Single Wall Connector - Residential

Alcove:  Min. Height  7 1/2'(2.29m)
 

Max. Depth  4'(1.22m)

Double Wall Connector - Mobile Home

Summary of Contents for SPECTRUM

Page 1: ...tioninstructions Contact local building or fire officials about restrictions and installation inspection requirements in your area TESTED and LISTED to CAN ULC S627 AND UL 1482 Meets the Environmental...

Page 2: ...ce 3 Maintenance Checks 4 Creosote 5 Formation and Need for Removal 5 Chimney Fires 5 In Case of a Chimney Fire 5 Avoiding a Chimney Fire 5 Assembly 6 Crate Removal 6 Optional Ash Cleanout System Inst...

Page 3: ...tained in good condition Periodically inspect seals and replace if neces sary Follow instructions included in the DR31 WDGKIT kit obtainable from your nearest Pacific Energy dealer 5 DOOR GLASS Do not...

Page 4: ...himney System Top baffle board blanket Baffle Top heat shield and mounting bolt Baffle Gasket Brick Rails Manifold Blower The blower should be cleaned out a minimum every six months by using a vacumn...

Page 5: ...nd must be lived with Regular inspection and cleaning is the solution The use of dry seasoned wood and ample combustion air will help to minimize the buildup Chimney Fires The result of excessive creo...

Page 6: ...at secure stove body to bottom pallet 4 Place stove body carefully on its back 5 Using two 3 4 wrench remove 1 x 1 2 bolts and save for later use 6 Remove pallet retaining brackets from stove bottom O...

Page 7: ...leaks 6 Install connector as per manufacturer s instructions 7 Attach stove to flooring using two 1 4 x 2 or longer lag screws Mobile Home Installation Warning Undernocircumstancesisthisheatertobeins...

Page 8: ...ney Support 56 1422 mm Minimum Minimum 7 2 1m Ceiling Height Attachment to floor for mobile homes Non combustible floor protector 48 1219 mm 3 914 mm Minimum Hooded vent or 90 elbow turned down The ch...

Page 9: ...ffect stove performance Chimney flue exit is to be 3 feet 1 m above roof and two feet 0 6 m above highest projection within 10 feet 3 m The installation must meet all local codes Do not connect this u...

Page 10: ...equires the unit to be secured to the structure to prevent dislodging of the air duct To draw outside air from behind the stove an outside air adaptor may be required see Optional Blower section Cut o...

Page 11: ...for the first 2 3 times it is very important that the room be well ventilated Open all windows and doors Smoke and fumes caused by the curing process may cause discomfort to some individuals Lighting...

Page 12: ...Overnight Burns 1 Open door and rake hot embers towards the front of the heater Add a couple of dry split logs on top of embers close door 2 Adjust air control to high and in just a few minutes logs...

Page 13: ...perate as follows Air control set to L low operate blower speed control on Low Air control set between L and H low and high oper ate blower speed control at desired setting Automatic To operate the bl...

Page 14: ...latch Excessive Creosote Buildup See 1 2 3 above Low Heat Output 1 Wood is wet Use dry wood 2 Fire too small Build a larger fire 3 Draft too low Chimney plugged or restricted inspect and clean Won t B...

Page 15: ...Door Handle Assembly WODC 4147C 11 Boost Manifold 4105 12 Firebrick Set BRIC SSERA 13a Brick Rail Left Right SSER RAILSET 14 Replacement Baffle Kit SSER DBAKIT 15 Baffle Pin SSER 125001 16 Baffle Gas...

Page 16: ...kel CAST 31NI Door Casting Radiant Nickel CAST 31RSNI 12 Door Handle Assembly WODC 4147C 13 Boost Manifold 4105 14 Firebrick Set BRIC SSERA 15a Brick Rail Left Right SSER RAILSET 16 Replacement Baffle...

Page 17: ...ng the basic functions of this design Traditional wood stoves had a basic combustion system which allowed a considerable amount of heat energy to escape up the chimney as unburned gases and particulat...

Page 18: ...ts back 5 Using a 3 4 wrench remove 1 x 1 2 bolts and save for later use 6 Remove pallet retaining brackets from stove bottom Pedestal Kit 1 With the unit on its back and the removable cover facing up...

Page 19: ...either A B C as shown below if you are installing the optional ash cleanout system or 1 full brick in place of A B if you are not installing the ash cleanout system Next install the side firebricks 4...

Page 20: ...20 SUPER SD1 280514 24...

Page 21: ...280514 24 SUPER SD1 21...

Page 22: ...22 SUPER SD1 280514 24...

Page 23: ...07 INSTALLEZ ET UTILISEZ SELON LES INSTRUCTIONS D INSTALLATION ET D OP RATION FOURNI AVEC L APPAREIL CONTACTEZ LES OFFICIELS DE LA CONSTRUCTION OU DE SERVICE D INCENDIE POUR DES INFORMATIONS QUANT AUX...

Page 24: ...PACIFIC ENERGY FIREPLACE PRODUCTS LTD 2975 Allenby Rd Duncan B C V9L 6V8 Phone 250 748 1184 Web site http www pacificenergy net Printed in Canada...

Reviews: