Calibration and Adjustment:

 

To field adjust the RSIC-SI-CRC EZ clip, rotate the Screw attaching 
the RSIC-SI-CRC EZ clip to the spring. Clockwise to raise. In 
converse rotate the screw counter clockwise to lower. Lowering the 
RSIC-1 clip will not loosen the spring. To adjust the spring itself you 
will need to hold the top Cup washer and turn the threaded rod from 
the top side.

 

The Pre-Calibration of the RSIC-SI-CRC EZ clip is designed to 
deflect only 1/2” from its pre-loaded (pre-set) position after the 2nd 
layer gypsum board has been installed.

Ceilings: 

 

IF required add strong back consisting of 1.5” Cold Rolled Channel 
or 2 pieces of drywall furring channel nested together, on the top side 
of the standard drywall furring channel to assist in leveling the 
ceiling at or near the perimeter. The strong back shall be placed 
perpendicular to the main drywall furring channels 

 

Install the gypsum board to the drywall furring channel leaving a 1/
8” to 1/4”  gap around the perimeter of the entire ceiling.

 

Caulk around the entire perimeter of the ceiling wall intersection.

 

 Use fire and smoke rated acoustical sealant where required. 

 

The RSIC-SI-CRC EZ is engineered for use with a minimum of 2 
layers of 5/8” gypsum board.

 

* RSIC OHD Adapter used for attaching directly to Concrete

General Information:

 

Resilient Sound Isolation Clip Spring Isolator (RSIC-SI-CRC EZ), 
furring channel (hat track) and gypsum board shall not carry heavy 
loads such as Projectors, HVAC Ducting, Curtains, etc. For these 
items use additional RSIC isolation clips specifically designed for 
that purpose.

 

Splice furring channel (hat track) with 6 inch overlap in mid span, 
secure with 18 ga. tie wire or with two framing screws (7/16”)

 

Seal all potential air leaks with non-hardening acoustical caulking to 
achieve best noise control results. Use fire rated sealant where 
required.

 

When attaching the RSIC-SI-CRC EZ clips to a steel Joist the 
minimum allowable thickness is 20 ga. (0.030).

Fire Test Information: