RSIC-SI-CRC EZ SOUND ISOLATION CLIP
PAC International, LLC. All Rights Reserved.
• (866) 774-2100 • Fax (866) 649-2710
RSIC® is a registered Trade Mark of PAC International, LLC.
PAC International, Inc. Tel: (866) 774-2100 Technical: (866) 649-2710 Web Site: www.pac-intl.com
Calibration and Adjustment:
To field adjust the RSIC-SI-CRC EZ clip, rotate the Screw attaching
the RSIC-SI-CRC EZ clip to the spring. Clockwise to raise. In
converse rotate the screw counter clockwise to lower. Lowering the
RSIC-1 clip will not loosen the spring. To adjust the spring itself you
will need to hold the top Cup washer and turn the threaded rod from
the top side.
The Pre-Calibration of the RSIC-SI-CRC EZ clip is designed to
deflect only 1/2” from its pre-loaded (pre-set) position after the 2nd
layer gypsum board has been installed.
Ceilings:
IF required add strong back consisting of 1.5” Cold Rolled Channel
or 2 pieces of drywall furring channel nested together, on the top side
of the standard drywall furring channel to assist in leveling the
ceiling at or near the perimeter. The strong back shall be placed
perpendicular to the main drywall furring channels
Install the gypsum board to the drywall furring channel leaving a 1/
8” to 1/4” gap around the perimeter of the entire ceiling.
Caulk around the entire perimeter of the ceiling wall intersection.
Use fire and smoke rated acoustical sealant where required.
The RSIC-SI-CRC EZ is engineered for use with a minimum of 2
layers of 5/8” gypsum board.
* RSIC OHD Adapter used for attaching directly to Concrete
General Information:
Resilient Sound Isolation Clip Spring Isolator (RSIC-SI-CRC EZ),
furring channel (hat track) and gypsum board shall not carry heavy
loads such as Projectors, HVAC Ducting, Curtains, etc. For these
items use additional RSIC isolation clips specifically designed for
that purpose.
Splice furring channel (hat track) with 6 inch overlap in mid span,
secure with 18 ga. tie wire or with two framing screws (7/16”)
Seal all potential air leaks with non-hardening acoustical caulking to
achieve best noise control results. Use fire rated sealant where
required.
When attaching the RSIC-SI-CRC EZ clips to a steel Joist the
minimum allowable thickness is 20 ga. (0.030).
Fire Test Information:
WWW.PAC-INTL.COM
Check UL Fire Resistance Directory File # R16638
Check UL’s web pages.
www.ul.com/database
Contact UL (877) UL– HELPS