17
5) By-pass control
According to inside and outside temperatures, the TAC4 DM control will monitor the opening/closing of the
bypass damper. A servo-motor (SMO) will have to be installed (option).
Operating description:
Opening of by-pass(*) if all following conditions are met:
-
Outside T° (sensor T1) < inside T° (sensor T2) – 1°C.
-
Outside T° (sensor T1) > 15°C.
-
Inside T° (sensor T2) > 22°C.
Closing of by-pass if one of the following conditions is met:
-
Outside T° (sensor T1) > inside T° (sensor T2).
-
Outside T° (sensor T1) < 14°C.
-
Inside T° (sensor T2) < 20°C.
All these temperature SET values can be modified using ADVANCED SETUP (see
www.lemmens.com
).
(*)When the bypass is opened, the pressure alarm is not activated.
LED BYPASS OFF
By-pass closed
R1
LED BYPASS ON
By-pass open
R1
6) Configuration
Configuration of the fan is made using the LCD display and the 4 setup knobs. SETUP,
↑
,
↓
and ENTER.
To start the configuration press SETUP until SETUP text appears on the LCD.
The principle of selection is to use keys
↑
and
↓
to make the choice and to press ENTER to confirm. The numbers
are introduced figure by figure.
Complete information is available on the PLC website:
www.lemmens.com
1
LANGUAGE
Language choice
2
FAN TYPE
Choice of fan through (CID – see label on fan)
3
MODE
Choice of working mode (CA, LS, CPs)
If MODE CA
4
m³h K1?
Type in supply airflow 1 (contact between K1 and +12V closed)
5
m³h K2?
Type in supply airflow 2 (contact between K2 and +12V closed)
6
m³h K3?
Type in supply airflow 3 (contact between K3 and +12V closed)
If MODE LS
4
V min?
Select minimum voltage value for LS link
5
V max?
Select maximum voltage value for LS link
6
m³/h
≡
Vmin
Select airflow corresponding to Vmin
7
m³/h
≡
Vmin
Select airflow corresponding to Vmax
8
% on K3?
Select multiplier of airflow when ter12V and K3 are closed (‘night’ setup).
NEXT if MODE CA or LS
9
%EXH/SUP
Choose the rate between the exhaust airflow (fan F2) and the supply airflow (fan F1)
10
CONFIG
TIME? N
Select Y to configure time and date
11
TIME
SEGMENT? N
Select Y to activate the time segment scheduling function
Complete information is available on the PLC website :
www.lemmens.com
Summary of Contents for CB2 TAC4 REC
Page 1: ...KLIMAATTECHNIEK Als het om lucht gaat T 0320 28 61 81 www auerhaan klimaattechniek nl...
Page 2: ...2...
Page 20: ...26 5 Sorties alarmes Alarmen uitgangen Alarms outputs Alarm Ausg nge...
Page 21: ...27...
Page 22: ...28...