5) By-pass control 

 
According to inside and outside temperatures, the TAC4 DM control will monitor the opening/closing of the 
bypass damper. A servo-motor (SMO) will have to be installed (option).  

 

Operating description: 
 
Opening of by-pass(*) if all following conditions are met:  

-

  Outside T° (sensor T1)  <  inside T° (sensor T2) – 1°C. 

-

  Outside T° (sensor T1)  >  15°C. 

-

  Inside T° (sensor T2)  >  22°C. 

 
Closing of by-pass if one of the following conditions is met:  

-

  Outside T° (sensor T1)  >  inside T° (sensor T2). 

-

  Outside T° (sensor T1)  <  14°C. 

-

  Inside T° (sensor T2)  <  20°C. 

 
All these temperature SET values can be modified using ADVANCED SETUP (see 

www.lemmens.com

). 

(*)When the bypass is opened, the pressure alarm is not activated. 
 

LED BYPASS OFF 

 

By-pass closed 

R1

 

LED BYPASS ON 

By-pass open 

R1

 

6) Configuration  

 
Configuration of the fan is made using the LCD display and the 4 setup knobs. SETUP,

 

 and ENTER. 

To start the configuration press SETUP until SETUP text appears on the LCD. 
The principle of selection is to use keys 

and 

 to make the choice and to press ENTER to confirm. The numbers 

are introduced figure by figure. 
 
Complete information is available on the PLC website:  

www.lemmens.com

 

 

LANGUAGE 

Language choice 

FAN TYPE 

Choice of fan through (CID – see label on fan)  

MODE 

Choice of working mode (CA, LS, CPs) 

 
If MODE CA 

m³h K1? 

Type in supply airflow 1 (contact between K1 and +12V closed) 

m³h K2? 

Type in supply airflow 2 (contact between K2 and +12V closed) 

m³h K3? 

Type in supply airflow 3 (contact between K3 and +12V closed) 

 
If MODE LS 

V min? 

Select minimum voltage value for LS link 

V max? 

Select maximum voltage value for LS link 

m³/h

Vmin 

Select airflow corresponding to Vmin 

m³/h

Vmin 

Select airflow corresponding to Vmax 

% on K3? 

Select multiplier of airflow when ter12V and K3 are closed (‘night’ setup). 

 
NEXT if MODE CA or LS  

%EXH/SUP 

Choose the rate between the exhaust airflow (fan F2) and the supply airflow (fan F1) 

10 

CONFIG 
TIME? N 

Select Y to configure time and date 

11 

TIME 
SEGMENT? N 

Select  Y to activate the time segment scheduling function 
Complete information is available on the PLC website :  

www.lemmens.com

 

Summary of Contents for CB2 TAC4 REC

Page 1: ...KLIMAATTECHNIEK Als het om lucht gaat T 0320 28 61 81 www auerhaan klimaattechniek nl...

Page 2: ...2...

Page 3: ...ient te gebeuren via de ingangen K1 K2 K3 softstop en niet door de 230V voeding te onderbreken 3 Werkingsmodes De controlebox CB2 TAC4 REC kan in 3 modes geconfigureerd worden MODE CA De installateur...

Page 4: ...tor 1 bepaald Bij door T3 gemeten temperaturen hoger dan 5 C de instructie uit de SETUP wordt niet be nvloed Bij door T3 gemeten temperaturen tussen 5 C en 1 C de instructie uit de SETUP wordt als vol...

Page 5: ...te bevestigen Getallen worden cijfer per cijfer gevormd Hieronder vindt u de eenvoudigde configuratie in geval van gebruik van n ventilator Voor een compleet technisch overzicht kan u op onze website...

Page 6: ...ie 10 INIT via DEBIET Mogelijkheid om een constante referentiedrukwaarde in te stellen ofwel automatisch op basis van het debiet ofwel manueel door de gewenste drukwaarde in te geven In geval van INIT...

Page 7: ...het circuit of de motor de oorzaak van het probleem is 1 2 DRUK ALARM Signaleert een drukalarm op ventilator In dit geval zal het LED alarm oplichten Het R2 relais van optie SAT3 zal sluiten en het LE...

Page 8: ...e tekst verschijnt in meerdere opeenvolgende keren op het scherm 9 Technische gegevens Voeding 230VAC tussen 208V en 240V Frequency 50 60Hz Aarding VERPLICHT Electrische beveiliging De motor is intern...

Page 9: ...the fan must be activated with entries K1 K2 K3 softstop and not via power supply 230V 3 Working modes The control box CB2 TAC4 REC allows operating in 3 different modes CA MODE The user defines 3 co...

Page 10: ...measured after the heat exchanger sensor T3 T T3 5 C the assigned airflow is as defined by SETUP 1 C T T3 5 C the airflow assigned by SETUP is automatically modified as follows If CA or LS working mod...

Page 11: ...lection is to use keys and to make the choice and to press ENTER to confirm The numbers are introduced figure by figure Complete information is available on the PLC website www lemmens com 1 LANGUAGE...

Page 12: ...s com 9 INIT CPs REF Setup of CPs fan pressure instruction 10 INIT via AIRFLOW Define if the constant pressure assignment value V for the fans is to be automatically determined as a consequence of a s...

Page 13: ...used by defective wire control circuit or motor 1 2 PRESSURE ALARM It signals a fan pressure alarm Alarm LED is lit R2 relay on SAT3 option is closed and the LED over the SAT3 relay is lit 1 3 Pa INIT...

Page 14: ...veral successive screens 9 Technical Data Supply 230VAC between 208V and 240V Frequency 50 60Hz Grounding COMPULSORY Electrical protection The motor is self protected against overloading It is thus NO...

Page 15: ...E BIJLAGE APPENDIX ANHANG Sch mas de raccordement Aansluitingsschema s Wiring diagrams Anschlusspl ne 1 Sch ma du circuit TAC4 DM schema van de TAC4 DM print TAC4 DM circuit diagram Schema der TAC4 DM...

Page 16: ...de ventilatoren Wiring of the fans Anschluss des Ventilators 2 1 Pulsion 2 2 Extraction DD 146 210 TAC 180W CID 720114 DS 140 59 TAC 230W CID 720124 Cfr 2 3 AUTRE OTHER DD 146 210 TAC 180W CID 720114...

Page 17: ...connections Anschl sse Ventilateur Ventilator Fan CC TAC4 EC Bleu Blauw Blue Blau Noir Zwart Black Schwarz Jaune Geel Yellow Gelb Blanc Wit Withe Weiss Blanc Wit Withe Weiss Rouge Rood Red Rot Rouge R...

Page 18: ...eschl Vol m 3 h K1 K2 geschl Vol m 3 h K2 K3 geschl Vol m 3 h K3 K1 K2 K3 offen softstop 3 2 Raccordement de plusieurs circuits en parall le Aansluiting van meerdere ventilatoren in parallel Wiring of...

Page 19: ...pen op K3 inactief K1 geschl softstart K1 offen softstop K2 0 10 V Signal K1 K3 geschl K3 aktiv K3 offen K3 inaktiv 4 2 Raccordement de plusieurs circuits en parall le Aansluiting van meerdere ventila...

Page 20: ...26 5 Sorties alarmes Alarmen uitgangen Alarms outputs Alarm Ausg nge...

Page 21: ...27...

Page 22: ...28...

Reviews: