14
3.4 User Setting
User settings menu includes five sub-menu: Communication Settings, Function Settings,
Protection Settings, Password Settings, and Recovery Settings.
Note: You need a password to enter user setting menu. The default password is
"
12345678
"
.
3.4.1 Communication Setting
1
.
Baud Rate
:
9600bps
▼
2
.
CRC Alignment
:
Litt Endian
▼
3
.
Modbus Address
:
0x01
Table 16: Communication setting
Communication setting parameters:
Baud rate: Supports five baud rates: 9600bps, 19200bps, 57600bps, 115200bps and
230400bps. The default is 9600bps;
CRC alignment: THE CRC can be emitted as "small-endian" or "big-endian", with the
default "small-endian";
Modbus address: address range 1-247, default address is "1";
3.4.2 Function Setting
1
.
Startup Mode
:
Local
▼
2
.
Rise Time Of Volt
:
XXXXX
mS
▼
3
.
Fall Time Of Volt
:
XXXXX
mS
▼
4
.
Rise Time Of Curr
:
XXXXX
mS
▼
5
.
Fall Time Of Curr
:
XXXXX
mS
▼
6
.
Auto-Reco(Fault)
:
30
S
▼
Close
▼
7
.
Auto-Output(Gold)
:
30 S
Close
▼
8
.
Timing Output
:
》
9
.
Parallel/Series Connection
:
》
11
.
Interface Setting
:
》
Table 17: Function setting
Function setting parameters:
Startup mode: When the device switch is closed, the device is in local control or
remote control mode;
Rise/fall time of voltage: The slope of the voltage reference change, with options in
milliseconds, seconds and minutes. This parameter takes effect only on voltage
priority;
Rise/fall time of current: The slope of the output current reference change, with
options in milliseconds, seconds and minutes. This parameter takes effect only on