31
Unibox TQ-RTL R-Tronic
Installation
102273880-V01.08.2019
(1)
Block or stud wall
(2)
"Unibox TQ-RTL R-Tronic"
(3)
Plaster
(4)
Pipe conduit unit (separate accessory)
(5)
Edge insulating strip (separate acces-
sory)
(6)
Screed
(7)
Protective tube (separate accessory)
6.2 Installation of the "Unibox TQ-
RTL R-Tronic"
DANGER
Danger to life due to electric
current
Danger to life due to contact with live
components.
f
The electrical connection must
only be carried out by a qualified
electrician.
The "Unibox TQ-RTL R-Tronic"
must always be located at the end
of the surface temperature balance
circuit (see 3.3 on page 27).
4
3
2
6
2
3
4
5
1
Illust. 9: Connection
(1)
Radiator
(2)
Wireless thermostat "R-Tronic"
(3)
"Unibox TQ-RTL R-Tronic"
(4)
Surface temperature balance circuit
(5)
Supply
(6)
Return
1. Provide a branch from the supply pipe of
the two pipe heating system.
2. Lay the surface temperature balance
circuit.
Lay the heating circuit in a spiral
pattern to achieve an even heat
distribution.
3. Remove the protection cover of the "Uni-
box TQ-RTL R-Tronic" and the front cover
of the pipe conduit unit (you must refit the
protection cover and the front cover after
commissioning) and insert the "Unibox TQ-
RTL R-Tronic" into the pipe conduit unit.
4. Use the enclosed brackets (see 1.2 on
) to align and fix the "Unibox TQ-
RTL R-Tronic" in the pipe conduit unit.