background image

Valves, co systems

Four-way mixing valve

Installation instructions

Oventrop  four-way  mixing  valve  PN  10  up  to
110  °C,  with  infinitely  adjustable  bypass,  flat
sealing.

Model: Bronze body, regulating insert, cover and

shaft  of  mixing  valve  with  double  O-ring
seal made of brass.

Size:    DN 25 Item no. 135 09 54

DN 32 Item no. 135 09 55

Application:

Central  heating  systems  with  circulation  pump
PN 10 up to 110 °C for flow temperature control.
The supply pipe can be connected on the left or
right hand side.
Tailpipe sets are to be ordered separately.

Function:

The  four-way  mixing  valves  serve  to  control  the
flow temperature. The setting is carried out with
the help of an electromotive actuator. 
This way, a reduction of the dew point of the flue
gas  in  the  boiler  and  the  resulting  corrosion  are
avoided. For heating circuits which are operated
at  high  boiler  and  low  flow  temperature,  e.g.
underfloor  heating  systems,  the  mixing  valve  is
equipped  with  a  manually  adjustable  bypass.
This  bypass  constantly  adds  return  water  to  the
supply pipe.
By  using  a  mixing  valve  with  a  control  device,
the flow temperature is automatically adapted to
the heat demand.
In  combination  with  the  manually  adjustable
bypass,  a  vibration-free  control  is  possible  even
in systems with high boiler and low flow tempe-
rature.

Installation:

The  parallel  arrangement  of  the  supply  and
return  allows  a  space-saving  installation  of  the
mixing valve.
Connection  of  the  mixing  is  carried  out  with  the
help of G 1

1

/

2

or G 2 collar nuts or it is supplied

pre-assembled  on  the  boiler  connection  system
”Regumat M4”.

Setting of the manual bypass:

The  bypass  valve  can  be  set  with  the  help  of  a
screwdriver:
Slit in vertical position: bypass closed
Slit  in  horizontal  position:  bypass  completely
opened
The  corresponding  flow  temperature  can  be  set
by turning the slotted screw with a screwdriver.

Installation example “Regumat M4”

Supply

Return

Return

Supply

GB

G 1

1

2

G 1

1

2

3