background image

Valves, co systems

“R-Tronic RT B” (ENOCEAN)

Installation and operating instructions 

EN

•  Installation and commissioning must only be carried out by a 

qualified tradesman.

•  Read installation and operating instructions before installation 

and operation.

•  Hand installation and operating instructions over to the final user.
•  Read separate instructions of connected systems.

EEP  A5-10-02   
EEP  A5-10-03   
EEP  A5-10-04   

EEP A5-10-06   
EEP  A5-10-06  +RPS       

Summary of Contents for EEP A5-10-02

Page 1: ...ng must only be carried out by a qualified tradesman Read installation and operating instructions before installation and operation Hand installation and operating instructions over to the final user...

Page 2: ...Technical data 7 5 Installation 8 5 1 General installation advice 8 5 2 Wall attachment of fixing plate R Tronic RT B ENOCEAN battery operation 9 5 3 Wall attachment of fixing plate and flush mounted...

Page 3: ...lease check the delivery for completeness It consists of the following components Optional accessories for 230 V power supply R Tronic RT B ENOCEAN Wall bracket 2 x battery Installation and operating...

Page 4: ...Oventrop Stra e 1 D 59939 Olsberg Germany Phone 49 29 62 82 0 Fax 49 29 62 82 450 E mail mail oventrop de 2 3 General conditions of sales and delivery 2 2 Storage Dry max RH 70 free from dust Do not e...

Page 5: ...the wireless thermostat can be used for the control of freely definable special functions RPS telegram These functions such as the control of light on off and blinds up and down are not stored in the...

Page 6: ...gram sent to gateway Current supply via external power pack Fan speed 1 3 Warning symbol for notes and error messages Fan control active Turning Function selection via display Pressing Confirmation of...

Page 7: ...ion IP20 EN 60529 Protective system III Protective low voltage Ambient temperature 5 C up to 50 C Energy supply Battery type AA 1 5 V Mignon LR6 alkaline no rechargeable batteries optional mains opera...

Page 8: ...not affected by other heat sources such as sunlight or heating devices next to it in order to guarantee a high measuring accuracy The wireless thermostat cannot only be mounted onto a wall but can als...

Page 9: ...sert two AA 1 5 V Mignon batteries into the battery case The position of the batteries is specified by the markings 2 Screw the supplied fixing plate for the wireless thermostat horizontally onto the...

Page 10: ...fore installation of the flush mounted power pack 2 Assemble the electrical connection between the flush mounted power pack and the 230 Volt connection in the flush socket 3 Screw the fixing plate to...

Page 11: ...Mains adaptor X X The R Tronic is now ready for the teach in process see paragraph 6 2 NOTE The R Tronic is removed by pulling it vertically upward out of the table stands The wireless thermostat must...

Page 12: ...at the thermostat during commissioning The display controlled user navigation see next page shows the respective activation process for the individual EPP profiles Function EEP profile ACTUAL VALUE 1...

Page 13: ...IS FAN NO SPECIAL FUNCTION NO A5 10 06 RPS ENGLISH Turn menu button change selection Press menu button confirm selection SPECIAL FUNCTION YES ROOM OCCUPIED NO ROOM OCCUPIED YES A5 10 06 A5 10 03 FAN Y...

Page 14: ...al measurement of the room temperature ACTUAL value Setting of the new required temperature nominal value Turn the menu button to the right to increase the temperature Turn the menu button to the left...

Page 15: ...A5 10 04 FAN SPEED fan active manual fan operation via R Tronic Return key key for reducing a value FAN OFF is displayed after having pressed the key several times When set to AUTO see below fan cont...

Page 16: ...tions A5 10 06 RPS Switching between PRESENT HOME and ABSENT Press once quickly Function key Plus Press key quickly e g light on Press and hold key e g increase brightness Function key Minus Press key...

Page 17: ...ss thermostat will be teached in The EEP profile activated at the R Tronic must be supported by the gateway i e it must be able to control the corresponding function If this is not the case the teach...

Page 18: ...ivation and deactivation of the key lock Once the teach in process has been completed the key lock will be activated automatically and the padlock symbol will appear With the activated key lock the se...

Page 19: ...rrect profile can then be activated in the course of the new installation see paragraph 6 1 on page 12 1 Switch to the setup menu by pressing the menu button until BACKLIGHT will appear on the display...

Page 20: ...Function and commissioning R Tronic RT B ENOCEAN 20 24 4 4 Keep the Plus key pressed for some seconds X The thermostat is reset to the factory settings and can be reconfigured 5...

Page 21: ...CH IN see paragraph 6 2 Transmission interval 10 or 30 minutes Languages German English French Offset temperature 3 0 C up to 3 0 C compensation of physical influences impairing the measurement accura...

Page 22: ...the error messages BATTERY EMPTY REPLACE BATTERIES POWER SUPPLY DEFECT Power supply for R Tronic temporarily insufficient RADIO MODULE DEFECT INIT ERROR Initialisation error occurred MEMORY DEFECT Err...

Page 23: ...mperature warmer colder 2 Setting of the fan speed respectively the ventilation intensity 3 Activation and deactivation of the function Room occupied present absent 4 Control of special functions e g...

Page 24: ...D 59939 Olsberg Germany Phone 49 29 62 82 0 Fax 49 29 62 82 450 E mail mail oventrop de Internet www oventrop com For an overview of our global presence visit www oventrop de Subject to technical modi...