background image

Electromotive actuator 24 V 

Transport and storage

7

115801283-V01.01.2020

Protection class

IP54

Protective system

III according to EN 60730

Installation posi-

tion

360°

Weight

320 g

4.  Transport and storage

Temperature 

range

-0 °C - 50 °C

Relative  

air humidity

0 - 85 %, not condensing

Particles

Store dry and free from dust

Mechanical influ

-

ences

Protected from mechanical 

agitation

Weather influenc

-

es

Do not store outdoors

Protect from direct sunlight

Chemical influ

-

ences

Do not store together with 
aggressive fluids

5.  Installation

5.1  Initial installation

Make sure that there is enough space for the 
installation of the actuator.

CAUTION

Risk of burns due to hot components

An unprotected contact with hot components 

may lead to burns.

 

f

Wear safety gloves.

36

Illust. 3:  Installation position

1.  Fit the adapter set to your valve according to the 

enclosed installation instructions.

2.  Fit the actuator to the connection thread of the 

adapter.

3. 

Hand tighten the collar nut.

Avoid cross threading.

NOTICE

Damage to the actuator when tightening 

the collar nut with excessive torque

The actuator can be damaged and its 
be function impaired if the collar nut is 
over-tightened.

 

f

Hand tighten the collar nut. 

5.2  Commissioning

5.3 

Configuration of the DIP switches

 

f

Remove the casing cover.

 

f

Configure the DIP switches.

3

2

5

1

4

6

Illust. 4:  DIP switches

ON

OFF

(1)

Valve anti-blocking 

function ON

Valve anti-blocking 
function  
OFF

If installation conditions allow, the valve an

-

ti-blocking function can be activated during 
commissioning.

The valve anti-blocking function will prevent 

sticking of the stem if the valve is not activated 

over a longer period, e.g. during  the summer 

break of heating systems.

If the valve anti-blocking function is activated, 
the stem will be moved for a few seconds, if no 
stroke lift is carried out within 10 days.

It is not possible to use the 
valve anti-blocking function 

during 3 point control!

Summary of Contents for Aktor M 2P

Page 1: ...Valves controls systems Operating instructions EN Electromotive actuator Aktor M ST 2P 3P L 24 V...

Page 2: ......

Page 3: ...5 2 3 2 Risk of burns due to hot components and surfaces 5 2 3 3 Availability of the operating instructions 5 3 Technical description 6 3 1 Construction 6 3 2 Functional description 6 3 3 Technical d...

Page 4: ...ult of action 2 Safety related information 2 1 Correct use Safety in operation is only guaranteed if the product is used correctly The actuator may be used in indoor heating ventila tion and air condi...

Page 5: ...espeople are able to carry out any work on the described product professional ly User The user has to be informed by the qualified trades people as to the operation 2 3 2 Risk of burns due to hot comp...

Page 6: ...0 5 mA invertible 3 point open stop closed 2 point open closed Connection Fixed pre assembled cable 1 5 m 5 x 0 5 mm2 Motor deactiva tion Drive stem extending electronically retracting electronically...

Page 7: ...stallation instructions 2 Fit the actuator to the connection thread of the adapter 3 Hand tighten the collar nut Avoid cross threading NOTICE Damage to the actuator when tightening the collar nut with...

Page 8: ...r installation NOTICE Damage to the control technology due to a high peak load when switching the actua tor on f Use switching components which are designed for a short term peak load of up to 12 A f...

Page 9: ...stment stem with little force f Turn the adjustment stem back by half a turn as soon as you feel a resistance in the upper or lower stroke position NOTICE Damage to the actuator due to manual setting...

Page 10: ...e the actuator from the valve Also remove the adapter set if you do not re quire it any longer for this valve 9 Reinstallation The actuator must not be in the lower stroke position for correct install...

Page 11: ......

Page 12: ...OVENTROP GmbH Co KG Paul Oventrop Stra e 1 59939 Olsberg GERMANY www oventrop com 115801384 V01 01 2020...

Reviews: