3-3. Link Controller Initialization
U3-1021
3-4
11/98
Westinghouse Proprietary Class 2C
3. Connect an applicable cable from the LC module (J1 Programming Port) to the
personal computer (COM1 or COM2). (See Section 2 for additional
information on the cable to be used.)
4. Copy the following programs and files from Drive C on the PC to the floppy
disk in Drive A.
— RLCFLASH.EXE program (on RLC10A disk)
— RLCEXTPC.EXE program (on RLC20A disk)
— Any applicable LC executable programs
— Any applicable configuration files
5. Run RLCEXTPC.EXE from Drive A, using the command line syntax shown
below:
A:\>RLCEXTPC.EXE [port] [baud]
where:
port = COM1 or COM2 (default = COM1)
baud = 9600 or 19200 (default = 19200 with no jumper installed)
Note
If a baud rate of 9600 is desired, install a wire jumper
in the Base Unit terminal block of the LC module
between B7 and B8.
For example, the following command line specifies that the LC is linked to
COM1 and that the baud rate is 19200:
A:\>RLCEXTPC.EXE COM1 19200
If the port and baud rate are not specified, the default values will apply
(port = COM1, baud = 19200).
6. Reset the LC module by removing it from its Base Unit, waiting five seconds,
and then replacing it.