All LP cylinders to be used with this appliance must be:
a. Constructed and marked in accordance with the
specifications for LP-gas cylinders Standard, CAN/CSA
B339, Cylinders, Spheres and Tubes for the Transportation of
Dangerous Goods.
b. Provided with a listed overfilling prevention device.
c.
Provided with a cylinder connection device compatible with
the connection for outdoor cooking appliances.
d. The LP gas cylinder used for this appliance must not have a
capacity larger than 20lb. (9 kg).
e. Approximately 18” (46 cm) high & 12” (30 cm) diameter.
f. The use of an approved LP gas cylinder stabilizer, such as the
one included, must be used when using this appliance in order
to prevent the LP gas cylinder from tipping over.
ENCLOSURES FOR SELF-CONTAINED
LP GAS SYSTEMS:
An enclosure for an LP-gas cylinder shall be ventilated by
openings at both the upper and lower levels of the enclosure. This
shall be accompanied by one of the following:
a. One side of the enclosure shall be completely open; or
b. For an enclosure having four sides, a top, and a bottom:
At least two ventilation openings (see Part IV, Definitions) shall
be provided in the sidewalls of the enclosure, located within 5
in (217 mm) of the top of the enclosure, equally sized, spaced
at a minimum of 90 degrees (1.57 rad), and unobstructed. The
opening(s) shall have a total free area of not less than 1 in
2
per lb
(14.2 cm
2
per kg) of stored fuel capacity.
Ventilation opening(s) shall be provided at floor level of the
enclosure and shall have total free area of not less than 1/2 in
2
per
lb (7.1 cm
2
per kg) of stored fuel capacity. If ventilation openings
at floor level area are in the side wall, there shall be at least two
openings. The bottom of the openings shall be 1 in (25.4 mm) or
less from the floor level and the upper edge no more than 5 in
(127 mm) above the floor level. The openings shall be equally
sized, spaced at a minimum of 90 degrees (1.57 rad), and
unobstructed.
Every opening shall have minimum dimensions so as
to permit the entrance of a 1/8 in (3.2 mm) diameter rod.
Ventilation openings in sidewalls shall not communicate directly
with other enclosures of the appliance.
WARNING:
Ensure that the LP gas cylinder is kept at a minimum
distance of three feet (36 inches) away from the appliance.
LP Cylinder
Tank Ring
2. Gas Hose
Regulator
Heat Sensitive
Hand Wheel
Cylinder
Shut Off
Valve
Check Valve
Nipple with
Flow Limiting Device
1. Firebowl
Valve Coupling
3. Cylinder Valve
Coupling
Appliance
Tank Ring
Minimum 36”
LEAK TEST: Apply the solution to the LP gas delivery
system at points:
1. Firebowl Valve Coupling
2. Gas Hose Regulator
3. Cylinder Valve Coupling
Caution:
Trip Hazard