23
Outdoor Lifestyles by Hearth & Home Technologies, Inc. • Twilight-II-B • 2108-900 Rev. W • 5/12
Apply housewrap or building paper
For placement of combustible housewrap or building pa-
per and non-combustible sheathing for the outside wall
see Figures 7.5 and 7.6.
Special care should be taken when choosing building
materials for weather proofi ng (i.e. building wraps, seal-
ant tapes, liquid sealants, rubberized fl ashings, etc.).
All sealant materials or building wraps installed within 6
inches of the top and 1 inch on the sides of the fi replace
surround must be approved to a minimum temperature
of 225º F continuous exposure. Consult the material’s
manufacturer to ensure product compliance.
Figure 7.6
METAL FLASHING
TOP OF SURROUND
SIDE OF SURROUND
1 IN.
6 IN.
Figure 7.5 Outside View without Non-combustible Sheathing Shown
* NOTE:
All fi nishing materials on top of exterior sheathing
must be non-combustible for a minimum of 10-7/8 inches
above and 2-3/4 inches on both sides of the exterior face of
the appliance. This non-combustible fi nishing material can
be up to a maximum of 6 inches thick (6 inches maximum
horizontal overhang) to allow for brick and stone alcoves
(see Figure 10.5).
** NOTE:
Combustible house wrap or building paper
MUST
NOT
extend over the outside of non-combustible sheath-
ing, and
MAY
extend over the fl ashing behind non-com-
bustible sheathing a maximum of 1 inch. Use high temp
silicone or sealant recommended by the manufacturer of
the housewrap to seal between combustible sheathing
house wrap and non-combustible sheathing. The sealant
material used within 6 inches of the top and 1 inch on the
sides of the fi replace surround must be approved to a
minimum temperature of 225º F continuous exposure.
Figure 7.7 Exterior Installation Prior to Finishing
Risk of Fire
• Non-combustible clearances must be main-
tained.
• Sheetrock, wood or other combustibles must
NOT be used as sheathing or facing in the non-
combustible zone.
• See
Sections 5 and 10
for proper clearances.
• See
Section 1
for combustible /non-combus-
tible defi nitions.
Once the appliance is in place use enough high tempera-
ture silicone sealant or manufacturer specifi ed sealant
(approved to a minimum of 225º F) to make a water tight
seal between outdoor surround and exterior sheathing.
Face the perimeter of the appliance with non-combustible
sheathing over shroud fl anges and fl ashing. See Figure
7.7 for non-combustible zone.
WARNING
APPLIANCE
TL-TRIM KIT
HOOD
TOP HOOD
TOP OF
FIREPLACE
16-5/16 in.
WALL STUD
HOUSEWRAP
INSULATION
HOUSEWRAP
**
(BUILDING
PAPER) OVERLAP
FLASHING 1 in.
SHEATHING,
COMBUSTIBLE
FIREPLACE
HEADER
INSULATED
FRAMING
STANDOFF
NON-COMBUSTIBLE
*
SHEATHING
10-7/8 in.
FLASHING
HEADER
10-7/8 in.
= NON-COMBUSTIBLE ZONE
2-3/4 in.
2-3/4 in.
= SHEATHING
= 1 INCH HOUSEWRAP OVERLAP
FLASHING
SHEATHING
NON-COMBUSTIBLE ZONE