Outdoor Lifestyles by Hearth & Home Technologies Inc. • Dakota-AU • 4036-914 Rev H • 6/11
11
A. Mantel Projections
Figure 7.1 shows the minimum vertical dimension of fireplace mantels or other combustible projections above the top front
edge of the fireplace.
Mantel
B
A
2.13 m
minimum
ceiling height
Overhang
305 mm
max. combustible
mantel depth
Figure 7.1 Clearances to Combustible Mantels or other Combustibles above Fireplace
7
Finishing
If
A
is:
Then
B
must
be at least:
152 mm - 914 mm
660 mm
915 mm or more
457 mm