![Outback FXR2012A Operator'S Manual Download Page 54](http://html.mh-extra.com/html/outback/fxr2012a/fxr2012a_operators-manual_1660615054.webp)
Operation
54
900-0167-01-00 Rev A
Grid Use Time
The inverter system is capable of connecting to, or disconnecting from, the utility grid based on time
of day. It can also be programmed to connect at different times on weekdays and on weekends.
Load Grid Transfer
The inverter system is capable of connecting to, or disconnecting from, the utility grid based on load
size. This avoids undesirable battery discharge from excessive loads. It can also be programmed to
connect to the grid when the batteries reach a low voltage due to excessive discharge.
Table 6
Comparison of Grid Functions
Mode
Complete Grid
Recharge
System
Display
Connects
to Grid
Adjustability
Renewable
Energy
Location of
Function
Mini Grid
Yes
Required
initial setup
only
Low
Battery
Limited (many
settings are
automatic)
Must be larger
than inverter
Inverter
HBX
No
Remains
installed
Low
Battery
Full
Preferred to be
larger than
inverter
System
Grid Use
Time
Depending on
Duration
Remains
installed
Time of
Day
Full Not
required
System
Load Grid
Transfer
Depending on
Duration
Remains
installed
High Load
Full
Not required
System