Operation
900-0161-01-01 Rev B
19
Table 1
Summary of Input Modes
Mode Summary
Benefits
Cautions Intended
Charger
Generator
Accepts power
from an
irregular or
low-quality
AC source
Can use AC that may be
unusable in other modes
Can charge even with
poor generator or
low-quality AC source
Will pass irregular or
low-quality power to the
output; could damage
sensitive loads
Offset unavailable
Source:
Generator
Loads:
Non-
sensitive
devices
Performs three-stage
charge and goes
silent as specified by
settings.
Support
Adds battery
power to
augment an
AC source that
has limited
output
Can use battery power
in conjunction with
AC source
Offset operation sends
excess DC to loads
Drains batteries during
support; intended for
intermittent use only
May not function with
low-quality AC source
Source:
Grid or
Generator
Loads:
Can be
larger than
AC source
Performs three-stage
charge and goes
silent as specified by
user settings.
Grid
Tied
Inverter sells
excess power
(renewable) to
utility
Bidirectional input
Can reduce utility bills
and still provide backup
Offset
operation sends
excess DC to loads
Any additional
Offset
excess is sold to the grid
Requires utility approval
Other approvals may be
required depending on
electrical codes
Has exact requirements
for accepting AC input
Requires renewable
energy source
Source:
Grid
Loads:
Any type
Performs three-stage
charge and goes
silent as specified by
user settings.
UPS
In grid failure,
unit switches to
batteries with
fastest possible
response time
Quick backup for
sensitive devices during
grid outage
Uses higher idle power
than other modes
Search
function
unavailable
Offset unavailable
Source:
Grid
Loads:
PC, audio,
video, etc.
Performs three-stage
charge and goes
silent as specified by
user settings.
Backup
In grid failure,
unit switches
batteries to
support loads
Simple use compared
to other modes; often
used with generators for
this reason
Less idle power than
UPS
Does not drain battery as
in
Support
Has none of the special
functions described in
other modes
Source:
Grid or
Generator
Loads:
Any type
Performs three-stage
charge and goes
silent as specified by
user settings.
Mini Grid
Stays off grid
most of the
time; only uses
grid when
batteries low
Can minimize/eliminate
dependence on grid
Offset operation sends
excess DC to loads (but
only when on grid)
Will not work properly
unless renewable source
is above a certain size
Conflicts with related
modes in system display
Source:
Grid
Loads:
Any type
Performs three-stage
charge on reconnect;
if charger is disabled,
inverter emulates
charge cycle from
external source and
reacts accordingly
Grid Zero
On-grid but
actual grid use
is “zeroed out”
with battery and
renewable
power; does not
sell or charge
Can minimize/eliminate
dependence on grid
Offset operation sends
excess DC to loads at
adjustable rate
Remains on-grid to avoid
transfer problems
Discharges batteries
while remaining on grid
Will not work properly
unless renewable source
is above a certain size
Battery charger
inoperative
Source:
Grid
Loads:
Any type
Charger inoperative;
batteries must be
charged using an
external (renewable)
energy source
Summary of Contents for Radian GS4048A
Page 1: ...Radian Series Inverter Charger GS4048A GS8048A Operator s Manual ...
Page 6: ...Table of Contents 6 900 0161 01 01 Rev B THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 20: ...Operation 20 900 0161 01 01 Rev B NOTES ...
Page 56: ...Troubleshooting 56 900 0161 01 01 Rev B NOTES ...
Page 67: ...Specifications 900 0161 01 01 Rev B 67 NOTES ...