INSTALLATION GUIDE
Product code
I
n Al
I
n Cu
U
n
I
max Al
I
max Cu
U
max
VG03-0010
380 A
425 A
1000 V
-
-
-
Type
Screw size
Screw
1
M10
Tightening torque
M
busbar
6 Nm
16 mm
SW
1
5
(M
s
/ M
H1
/ M
H2
)
2,5-35 mm²
6 Nm
Screw
2
M8
6-50 mm²
10 Nm
SW
2
4
Min. Input busbar
1x(1x2
4
)
-
Max. Input busbar
10x(1x2
4
)
-
Max. Output cable
50 mm²
1,5 mm2
2,5 mm2
6 mm2
10 mm2
16 mm2
25 mm2
35 mm2
50 mm2
-
3/0
3/3
3/3
2/3
1/2
1/1
0/1
70 mm2
95 mm2
120 mm2
150 mm2
185 mm2
240 mm2
300 mm2
400 mm2
-
-
-
-
-
-
-
-
Product data
Product name
OJL-connector 400 FBB S
Installation
DIN-rail and screw mounting
Cross-section of conductors and max. number of conductors/ space (for Cu-conductors). ( H1 / H2 )
Connection
Stripping length (output)
L
1
L
1
SW
1,2
Scr
e
w
1,
2
Connect the
c
onductors when the cover is open. Only the copper busbars can be used in the input.
We recommend a ferrule when using a fine-stranded conductor.
Note! It's only allowed to use Cu-conductors for branching.
Input
S
M
s
M
H1
M
H2
Screw
1
Sw
1
Screw
2
Sw
2
Note! The specified max. amount of
conductors refers only to industrially
installed terminals.
Removing from
DIN-rail
Release the slider
part with a
screwdriver. Lift
the connector.
DIN-rail mounting
Set the connector
on a DIN-rail.
See picture.
Push until ”click”
Mounting with
screw
Max. Ø 5
Sealing
It is possible to seal
the cover after
connecting the
conductors.
Output
H
2
Output
H
1
Input
S