INSTALLATION GUIDE
Product code
U
n
VI02-0002
690 V
Method
Screw
Screw size
Thread
1
M12
Tightening torque
Stripping length
SW
1
5
(M
1
/ M
2
)
25-95 mm²
22 Nm
22 mm
Thread
2
M8
6-16 mm²
5 Nm
6 mm
SW
2
6
1,5-4 mm² (Test leads)
3,5 Nm
Max. Conductors
95 mm²
1,5 mm
2
2,5 mm
2
6 mm
2
10 mm
2
16 mm
2
25 mm
2
35 mm
2
50 mm
2
-
-
3
3
3 (1)
3 (1)
2 (1)
1 (1)
70 mm
2
95 mm
2
120 mm
2
150 mm
2
185 mm
2
240 mm
2
300 mm
2
400 mm
2
1 (1)
1 (1)
-
-
-
-
-
-
Cross-section of conductors and max. number of conductors/space. (Al-conductors in parenthesis)
Conductors
6xAl/Cu 6-95 mm2
Installation
Connection
Conductors
L
1
Test leads
L
2
Product data
Product name
OT-PEN connector 95 Al/Cu
L
1,2
SW
1,2
Th
read
1
,2
Both the copper- or aluminium conductors can be used in the
connection. Note! When using the aluminium conductor, it is
only allowed to use one conductor/space.
With the Al-conductors, it's recommended to use anti-
corrosion paste. (e.g. Penetrox)
We recommend a ferrule when using a fine-stranded
conductor.
M
2
M
1
Screw
2
Screw
1
Mounting with screw
Note! The specified amount of
conductors refers only to industrially
installed terminals.
TN-C (PEN) system can be transferred into TN-S (PE+N) system
by removing connector block. Connector is equipped with two
terminals for test leads.