Figure 4 - Threaded Rod Spacing Dimensions

 Vertical 

Air 

Discharge

Table 4 - Threaded Rod Spacing Dimensions

                        Vertical Air Discharge

Heater 

kW

Threaded

Rod

E

F

J

K

10.1 to 

20.0 kW

5/16 - 18 

12 in.

305 mm

5 in.

127 mm

6 in.

152 mm

4 3/4 in.
121 mm

Table 5 - Dimensions and Weight

Heater 

kW

Height

Width

Depth

Weight

10.1 to

20.0 kW

21 3/4 in.

553 mm

19 in.

483 mm

16 3/4 in.

413 mm

78 lb.
35 kg

WIRING

All wiring must be in accordance with National and Local 
Electrical Codes.

The heater must be grounded as a precaution against 
possible shock.

Insure power source is deenergized before wiring heater.

Check nameplate on back of heater. 

Connect heater only to voltage and phase specifi ed on 
nameplate.

Two knockouts are provided in the back of the heater.  
For supply power wiring a multiple 1 3/8 in. to 1 3/4 in. 
(35 mm to 44 mm) knockout is provided. 
For control wiring a 1/2 in. (13 mm) knockout is provided.

Field wiring must be properly sized to carry the amperage 
of the heater and all accessories.

Relay with Transformer (RT) – Low voltage thermostat 
wiring.

RT is located on back wall of heater control compartment. 
- Remove wiring separator.
- Remove knockout from heater back.
- Wire remote thermostat to RT.
- Replace wiring separator and tighten pipe nipple nut.

Wiring compartment volume: 85 in

3

 (1393 cm

3

) minimum.

HEATER OPERATION

Fan Delay

On a call for heat from either the remote (fl oor level) 
thermostat or the unit mounted thermostat the elements 
will be energized.

When the thermostat is satisfi ed the elements will 
be deenergized.

The fan will continue to run until the residual heat is 
removed from the heater. Then the fan will stop.

Automatic Reset Thermal High Limit

 

OHV heaters have an automatic reset thermal high limit 
that will deenergize the heating elements if the interior 
temperatures of heater exceed its setting. The limit will 
automatically reset when the heater interior temperatures 
fall below its setting.

SERVICE

The heater motor is permanently lubricated.

Occasional cleaning of the inlet grille will prevent 
clogging. Use a vacuum with a brush attachment.

WARRANTY

OUELLET CANADA INC. warrants the electric heating 
element of the 

OHV

 series for a one (1) year period; and 

their component parts against defects in material and 
workmanship for a one (1) year period following the date 
of purchase, under normal use and service, when proof 
of purchase of such is provided to the manufacturer. The 
obligation of Ouellet Canada Inc., under the terms of 
this warranty, will be to supply a new unit and this omits 
the manufacturer to bear the installation costs or other 
secondary charges linked to replacing the unit or the 
component part(s).

KEEP THIS INSTRUCTION PAMPHLET

FOR THE USER  INS238-201001-00

 IMPORTANT

Units with Optional Factory Installed Manual Reset 
Thermal High Limit only:

  Located on the back of the 

heater, the manual reset thermal high limit is wired in 
series with the automatic reset thermal high limit and will 
not reset until the heater has cooled and the reset button 
has been pushed in.

WIRING

 (continued)

The heater has a wiring diagram affi xed to the inside of 
the control compartment access door. Check this diagram 
before making any electrical connections.

Branch circuit wiring must be minimum 600 Volt, 60 °C.

Summary of Contents for OHV Series

Page 1: ... with the National Electrical Code See Figures 1 3 and Tables 1 3 for minimum mounting clearances CAUTION To prevent possible overheating or damage due to overheating keep at least 5 ft 1524 mm clearance in front of heater See Tables 1 3 for side ceiling and back minimum mounting clearances Wall Ceiling structures and anchoring provisions must be of sufficient strength to support the combined weigh...

Page 2: ... be energized After the elements get warm a short period of time the fan will come on 5 kW and less When the thermostat is satisfied the elements will be deenergized The fan will continue to run until the residual heat is removed from the heater Then the fan will stop Automatic Reset Thermal High Limit OHV heaters have an automatic reset thermal high limit that will deenergize the heating elements ...

Page 3: ...Use minimum 600 Volt 60 C wire only When installed heater must be electrically grounded in accordance with the National Electrical Code See Figures 1 3 and Tables 1 3 for minimum mounting clearances CAUTION To prevent possible overheating or damage due to overheating keep at least 5 ft 1524 mm clearance in front of heater See Tables 1 3 for side ceiling and back minimum mounting clearances Wall Ce...

Page 4: ...he fan will continue to run until the residual heat is removed from the heater Then the fan will stop Automatic Reset Thermal High Limit OHV heaters have an automatic reset thermal high limit that will deenergize the heating elements if the interior temperatures of heater exceed its setting The limit will automatically reset when the heater interior temperatures fall below its setting SERVICE The ...

Reviews: