18

OTHER CONSIDERATIONS

PIPE EXPANDING METHOD

Note: 

Improper pipe expanding is the main cause of refrigerant leakage.
Please expand the pipe according to the following steps:  

1. Cut the pipe

•  Confirm the pipe length according to the  

distance between indoor and outdoor unit.

•  Cut the pipe with pipe cutter.

 

2. Remove the burrs

•  Remove the burrs with a sharper and  

prevent the burrs from getting into the pipe.

  

3. Put on suitable insulating pipe 

4. Put on the union nut

•  Remove the union nut on the indoor connection 

pipe and outdoor valve; install the union nut on 
the pipe. 

 

pipe

pipe cutter

leaning

uneven

burr

pipe

shaper

downwards

union pipe

pipe

5. Expand the port

•  Expand the port with an expander.

 

Note: 

"A" varies according to the diameter, please refer to 
the chart below: 
 

Outer diameter 

 (mm)

A (mm)

Max

Min

Φ 6 - 6.35 (1/4’’)

1.3

0.7

Φ 9.52 (3/8’’)

1.6

1.0

Φ 12 - 12.7 (1/2’’)

1.8

1.0

Φ 15.8 - 16 (5/8’’)

2.4

2.2

6. Inspection

•  Check the quality of the expansion. If the surface 

is not smooth, repeat the previous steps. 

expander

pipe

hard

mold

smooth surface

the length is equal

improper expanding

leaning

crack

damaged

surface

uneven

thickness

Summary of Contents for MPD18KCH22S-O

Page 1: ...before operating the unit and keep it for future reference DUCTLESS MULTIZONE HEAT PUMP INS527 201801 01 Owner s Manual 22 21 SEER INVERTER 18 000 to 42 000 BTU hr Models MPD18KCH22S O MPD24KCH21S O...

Page 2: ...electrical connection 10 Installation 11 Installation of outdoor unit 11 Vacuum pumping 16 Checking after installation 17 Other consideration 18 IPipe expanding method 18 This appliance is not intende...

Page 3: ...on that if not avoided could result in serious injury or death Indicates a hazardous situation that if not avoided may result in minor or moderate injury Indicates important but not hazard related inf...

Page 4: ...wire is damaged it must be replaced by a quali ed person in order to avoid a hazard Do not wash with water to avoid electric shock Maintenance must be performed by quali ed person Otherwise it may cau...

Page 5: ...o electricity and safety Do not turn the power on before nishing installation If the power supply or signal control wires are damaged it must be replaced by a quali ed person in order to avoid problem...

Page 6: ...om animals or plants If it is unavoi dable please add a fence around the outdoor unit for safety purpose Instructions for installation and use of this product are provided by the manufacturer WORKING...

Page 7: ...loth or lightly moistened with water to wipe it Checking before usage 1 Check that air inlets and air outlets are not blocked 2 Check if circuit breaker and connection are in good condition 3 Check th...

Page 8: ...0 mm or more Air inlet side E 19 11 16 500 mm or more Space to the obstruction E 19 11 16 500 mm or more Space to the obstruction D 19 11 16 500 mm or more Air inlet side A 19 11 16 500 mm or more Spa...

Page 9: ...frequency devices such as welding machine medical equipment A place near coastal regions A place with oil or fumes in the air A place with sulphurous gas Other places with special environment Near a...

Page 10: ...e spaced out Cut o the power supply before proceeding any work related to electricity Do not turn on the power before nishing installation The temperature of refrigerant circuit will be high please ke...

Page 11: ...or unit in pits or air vents Notes Take su cient protective measures when installing the outdoor unit Make sure the support can withstand at least four times the unit weight The outdoor unit should be...

Page 12: ...sheet below NOTES If the pipe diameter of the outdoor unit doesn t match the piping connection size of the indoor unit use the piping connection size of the indoor unit and add the adaptor supplied w...

Page 13: ...ing cable To unit B Connecting cable To unit C Connecting cable To unit D Connecting cable To unit E Connecting cable Power cord L1 L2 C C D C E C L1 L2 L1 L2 To the power supply To unit B Power cord...

Page 14: ...nd maximum height di erence Outdoor unit Equivalent length of the farthest tting pipe Lx Indoor unit Indoor unit Height di erence between indoor unit and outdoor unit H1 Height di erence between indoo...

Page 15: ...refrigerant for the following total piping lengths Model Pre charge length ft m MPD18KCH22S O 33 10 MPD24KCH21S O 98 30 MPD30KCH21S O 130 40 MPD36KCH21S O 130 40 MPD42KCH21S O 130 40 For pipe runs ove...

Page 16: ...been reached 5 With the vacuum pump still in operation close the low pressure knob on the vacuum pump coupling Stop the vacuum pump 6 Open the 2 way valve by 1 4 turn and then close it after 10 second...

Page 17: ...ric wiring and pipes installed correctly It may cause malfunction or damaging the parts Is the unit grounded securely It may cause electric leakage Does the power wire follow the speci cations It may...

Page 18: ...union nut Remove the union nut on the indoor connection pipe and outdoor valve install the union nut on the pipe pipe pipe cutter leaning uneven burr pipe shaper downwards union pipe pipe 5 Expand the...

Reviews: