S O U N D D A T A
TKC/TKS 300 EC
LpA
LwA tot dB (A)
63
125
250
500
1K
2K
4K
8K
10V, 78 l/s, 380 Pa
Environment
65
72
38
47
58
62
68
67
60
51
Inlet
74
58
66
69
67
66
64
62
52
8V, 63 l/s, 230 Pa
Environment
58
65
33
42
51
56
61
60
53
41
Inlet
68
55
63
61
61
59
58
54
43
6V, 46 l/s, 130 Pa
Environment
51
58
30
36
43
50
55
53
42
32
Inlet
62
51
57
53
55
51
50
43
31
4V, 38 l/s, 60 Pa
Environment
41
48
50
49
40
35
40
35
31
21
Inlet
53
47
48
45
46
43
38
31
15
TKC/TKS 400 EC
LpA
LwA tot dB (A)
63
125
250
500
1K
2K
4K
8K
10V, 167 l/s, 350 Pa
Environment
68
75
43
54
65
69
70
69
65
56
Inlet
79
61
71
73
73
70
71
69
60
8V, 144 l/s, 255 Pa
Environment
64
71
41
52
61
65
66
65
62
51
Inlet
76
59
69
70
69
66
67
64
55
7V, 123 l/s, 185 Pa
Environment
61
68
40
49
56
61
63
61
57
45
Inlet
73
58
68
66
65
63
63
59
49
5,5V, 89 l/s, 105 Pa
Environment
54
61
50
49
40
35
40
35
31
21
Inlet
65
55
59
56
58
56
58
47
37
The sound data have been compiled by means of sound
measurements methods as follows:
Pressure and drop: SS-ISO 5801.
Determination of acoustic sound level in duct:
SS-EN ISO 5136.
Determination of acoustic sound level in reverberation
room: SS-EN ISO 3741.
D E S I G N A T I O N S
LwATot
: Total A-weighted sound power level dB(A)
(ref 10
-12
W)
=
the sum of the sound power level in the
octave ranges.
LwA
: A-weighted sound power level in octave range
dB(A)(ref 10
-12
W).
LpA
: A-weighted sound pressure level in dB(A) accor-
ding to normed A-weightening correction and relating
to an effective absorption area of 20 m
2
with half sphe-
rical translation at a distance of 3 metres.
17