F A U L T D E T E C T I O N
1. Make sure that there is power to the fan.
2. Cut the power and verify that the impeller is not
blocked.
3. Check the thermal contact (for AC). If it is discon-
nected the cause of overheating must be taken care
of, not to be repeated. To restore the manual ther-
mal contact, cut the power for a couple of
minutes. Larger motors than 1,6 A may have manu-
al resetting on the motor. If it has automatic thermal
contact the resetting will be done automatically
when the motor has cooled.
4. Make sure that the capacitor is connected according
to the wiring diagram (for AC).
5. If the fan still does not work, the first thing to do is
to change the capacitor (for AC).
6. Check the LED flashing code (do not apply for RKB
300x150 B1 EC, RKB 400x200 C1 EC, RKB 500x
250 B1 EC, RKB 500x250 E1 EC, RKB 600x300 A1
EC). For more information see page 54-55.
7. If nothing of this works, contact your fan supplier.
8. If the fan is returned to the supplier, it must be
cleaned, the motor cable undamaged and a detailed
nonconformity report enclosed.
W A R R A N T Y
M A I N T E N A N C E
• Before service, maintenance or repair begins, the fan
must be tension free and the impeller must have
stopped.
• Consider the weight of the fan when removing or
opening larger fans to avoid jamming and contu-
sions.
• The fan must be cleaned when needed, at least once
per year to maintain the capacity and to avoid unba-
lance which may cause unnecessary damages on the
bearings.
• The fan bearings are maintenance-free and should
be renewed only when necessary.
• When cleaning the fan, pressure wash or strong dis-
solvent must not be used. Cleaning should be done
without dislodging or damaging the impeller
.
• Make sure that there is no noise from the fan.
O P E R A T I O N
When starting, make sure that:
• the current does not exceed more than +5% of what
is stated on the label.
• the connecting voltage is in b6% to –10%
of the rated voltage.
• no noise appears when starting the fan.
• the rotation direction at 3-phase motors are accor-
ding to the label.
H O W T O H A N D L E
• The fan must be transported in its packing until in-
stallation. This prevents transport damages, scrat-
ches and the fan from getting dirty.
• Attention, look out for sharp edges and corners.
•
Attention!
Temperatures up to 85°C can be pre-
sent on the controller housing (only for EC motor).
•
Waiting period of at least 3 minutes!
(only for
EC motor) Because of internal capacitors, danger of
death exists even after switching off the device
through directly touching the energized parts or due
to parts that have become energized due to faults.
The controller housing may only be removed or
opened when the power line has been switched off
and a period of three minutes has elapsed since swit-
ching it off.
• Avoid extreme heat or cold (temperature range for
storage and transport.
• Avoid prolonged storage; we recommend a maxi-
mum of one year (consult the manufacturer before
starting if stored for longer).