13
S O U N D D A T A
LPKB 125 B, 75 l/s 180 Pa
LpA
LwA tot dB (A)
63
125
250
500
1K
2K
4K
8K
Environment
52
59
27
34
57
51
47
43
36
29
Inlet
68
48
59
62
65
56
51
52
45
Outlet
71
53
60
67
67
63
58
55
48
LPKB 125 B-r, 50 l/s 90 Pa
Environment
40
47
22
28
44
43
39
35
28
25
Inlet
63
43
53
60
57
48
43
42
32
Outlet
66
47
54
64
58
54
49
45
35
LPKB 160 K, 75 l/s 175 Pa
Environment
50
57
26
34
53
52
46
42
36
30
Inlet
69
51
60
65
64
57
54
53
48
Outlet
71
55
62
67
67
62
58
55
48
LPKB 160 K-r, 55 l/s 80 Pa
Environment
41
48
23
28
43
44
37
34
27
25
Inlet
61
43
53
57
56
48
45
41
34
Outlet
64
48
53
61
57
52
49
44
34
LPKB 200 B, 120 l/s 250 Pa
Environment
52
59
26
39
51
57
47
47
40
31
Inlet
72
54
62
66
69
59
58
58
49
Outlet
75
56
62
67
71
64
66
62
51
LPKB 200 B-r, 60 l/s 100 Pa
Environment
38
45
23
32
40
42
35
34
27
26
Inlet
60
46
54
54
55
47
43
40
28
Outlet
62
48
54
57
57
50
51
43
30
LPKB 200 K, 135 l/s 250 Pa
Environment
55
62
30
41
51
61
50
48
43
36
Inlet
74
54
64
64
73
61
59
60
56
Outlet
78
59
65
67
75
68
67
64
58
LPKB 200 K-r, 100 l/s 100 Pa
Environment
44
51
27
40
47
47
40
38
32
27
Inlet
66
50
60
59
62
51
49
50
43
Outlet
68
53
59
62
64
57
57
53
45
The sound data have been compiled by means of sound
measurements methods as follows:
Pressure and drop: SS-ISO 5801.
Determination of acoustic sound level in duct:
SS-EN ISO 5136.
Determination of acoustic sound level in reverberation
room: SS-EN ISO 3741.
D E S I G N A T I O N S
LwATot
: Total A-weighted sound power level dB(A)
(ref 10
-12
W)
=
the sum of the sound power level in the
octave ranges.
LwA
: A-weighted sound power level in octave range
dB(A)(ref 10
-12
W).
LpA
: A-weighted sound pressure level in dB(A) accor-
ding to normed A-weightening correction and relating
to an effective absorption area of 20 m
2
with half sphe-
rical translation at a distance of 3 metres.