•  Before service, maintenance or repair, disconnect 
  power and wait until the impeller has stopped.
•  Consider the weight of the fan when removing or 
  opening larger fans to avoid injury and damage.
•   Attention, look out for sharp edges.
• 

Attention! 

Temperatures up to 85°C can be pre-

  sent on the controller housing (only for EC motor).
•  

Waiting period of at least 3 minutes! 

(only for 

  EC motor) Because of internal capacitors, danger of 
  death exists even after switching off the device 
 

through directly touching the energized parts or due 

  to parts that have become energized due to faults. 
  The controller housing may only be removed or  
  opened when the power line has been switched off 
  and a period of three minutes has elapsed since swit-
  ching it off.
•  The fan must be cleaned regularly, at least once 
  per year to maintain the capacity and to avoid unba-
  lance which may cause unnecessary damage of the 
 bearings.
•  The fan bearings are maintenance-free and should 
  be replaced only when necessary.
•   When cleaning the fan, pressure wash or strong dis-
  solvent must not be used. Cleaning should be done 
  without displacing or damaging the impeller

.

•   Make sure that there is no noise from the fan.

11

The fan is easy to open for 
cleaning and service with  the 
swing-out design.
Loosen the screws a few 
turns, without removing 
them.
Turn the motor bracket to the 
right so the screws can go 
through the key holes. Open 
the motor bracket.
When closing, turn the motor 
bracket to the left so the 
screws go into the smaller 
part of the keyholes.
Tighten the screws.

OPEN

OPEN

CLOSE

CLOSE

M A I N T E N A N C E

F A U L T   D E T E C T I O N

1.  Make sure that the power is connected to the fan.
2. Disconnect the power and verify that the impeller 
  is not blocked.
3. Check the thermal contact (for AC). If it is trig-
  gered the cause of overheating must be investigated 
  and taken care of.

 

To restore the manual thermo-

  protector the power must be disconnected for a 
  couple of minutes. Larger motors

 

than 1,6 A may 

 

have manual reset of the motor. In case of automatic 

  thermo-protector the resetting will be done auto-
  matically when the motor has cooled down.

4.  Make sure that the capacitor is connected according 
  to the wiring diagram (for AC).
5.  If the fan still does not work, the first thing to do is 
  to replace the capacitor (for AC).
6. If the previous steps doesn’t solve the problem, 
  contact your fan supplier.
7. If the fan is returned to the supplier, it must be 
  cleaned, the motor cable must be undamaged and a 
  detailed fault description must be enclosed.

W A R R A N T Y

The warranty is only valid under condition that the 
fan is used according to this “Directions for  use” and 
a regular maintenance has been made and record. The 
warrantor is responsible only for the operation if app-

roved accessories are used. The warranty does not cover 
product failures caused by accessories/equipment from 
other manufacturers.

E N G L I S H

1270369_utg4_LPKB_LPFB_LPKB_Silent_SV_EN.indd   11

2020-01-07   13:03:43

1270369_utg4_LPKB_LPFB_LPKB_Silent_SV_EN.pdf   11

1270369_utg4_LPKB_LPFB_LPKB_Silent_SV_EN.pdf   11

2020-01-07   13:06:16

2020-01-07   13:06:16

Summary of Contents for LPFB

Page 1: ...rections for use LPKB LPFB LPKB Silent 1270369_utg4_LPKB_LPFB_LPKB_Silent_SV_EN indd 1 2020 01 07 13 02 58 1270369_utg4_LPKB_LPFB_LPKB_Silent_SV_EN pdf 1 1270369_utg4_LPKB_LPFB_LPKB_Silent_SV_EN pdf 1...

Page 2: ...r inte mnad f r anv ndning av personer inklusive barn med nedsatt fysisk sen sorisk eller mental f rm ga eller bristande erfaren het och kunskap om de ej vervakas eller instrue ras ang ende produktens...

Page 3: ...rollera att fl kten r monterad och elektriskt ansluten p r tt s tt med skyddsjord och motor skydd Till enfasfl ktar anv nds jordfelsbrytare typ A AC MOTOR F r varvtalsreglering av AC motor kan transfo...

Page 4: ...allationsanvisningar f r fr nluftsystem Montera fast eldosan p fl ktens l ngsida eller utloppsgaveln enl bilder Anv nd bifogad skruv som ligger i eldosan S V E N S K A 1270369_utg4_LPKB_LPFB_LPKB_Sile...

Page 5: ...n av nyckel h len ppna motorplattan Vid st ngning vrid motor plattan t v nster s att skru varna g r i den mindre delen av nyckelh len Skruva t PPNA PPNA ST NG ST NG S V E N S K A F E L S K N I N G 1 K...

Page 6: ...magnetisk kompatibilitet EMC Generella fordringar Immunitet hos utrustning i bost der kontor butiker och liknande milj er x EN 61000 6 2 2005 Elektromagnetisk kompatibilitet EMC Generella fordringar I...

Page 7: ...ectromagnetic compatibility EMC Generic standards Immunity for residential commercial and light industrial environments x EN 61000 6 2 2005 Electromagnetic compatibility EMC Generic standards Immunity...

Page 8: ...use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance The fan is used for transportation of clean air mea ning...

Page 9: ...if neces sary The internal poten tiometer should then be disconnected The EC motor has tachometer output one pulse per revolution EMC COMPATIBLE INSTALLATION OF EXTERNAL CONTROL LINES The control cabl...

Page 10: ...n instructions of exhaust systems 10 Mount the junction box on the long side or outlet side of the fan acc pictures Use the enclosed screws located in the junction box E N G L I S H 1270369_utg4_LPKB_...

Page 11: ...the left so the screws go into the smaller part of the keyholes Tighten the screws OPEN OPEN CLOSE CLOSE M A I N T E N A N C E F A U L T D E T E C T I O N 1 Make sure that the power is connected to t...

Page 12: ...Tel 46 226 860 00 Fax 46 226 860 05 Email info ostberg com www ostberg com 1270369_utg4_LPKB_LPFB_LPKB_Silent_SV_EN indd 12 2020 01 07 13 03 43 1270369_utg4_LPKB_LPFB_LPKB_Silent_SV_EN pdf 12 1270369_...

Reviews: