S E R V I C E M E N U : “ S E N S O R C A L I B R A T I O N ” :
Setting for calibration of temperature sensors using an offset value of +-10°C/+-50°F.
All temperature sensors will be adjusted to this value. It’s not possible to calibrate individual donor.
Press again and then in order to choose
Limit:
(+-10°C/+-50°F).
F
Freeze protection
Flow direction
Sensor calibration
Load/Save Settings
Sensor calibration
32°F
Sensor calibration
32°F
S E R V I C E M E N Y : “ V E R S I O N I N F O ”
Displays the software version of the unit (Heru) and the wireless control (RC).
Press
again to see the version.
S E R V I C E M E N U : “ L O A D / S A V E S E T T I N G S ”
"Load/Save" gives the installer the opportunity to save the set values in service menu after the installation, alt.
load previously saved values.
Press
again and then in order to choose
Load Settings
or
Save settings
.
After you have ”
load”
or
”Saved”
it may take a minute before the unit re-created connection to the wireless
control unit and the right data is displayed.
Flow direction
Sensor calibration
3.00
3.00
Sensor calibration
Load/Save Settings