Osram OTi30W Installation And Troubleshooting Manual Download Page 4

10/2018 

 

 

 

 

verify that the total forward voltage is within the limits of this product. Using a voltage meter, it 
may be possible to directly measure the voltage across the LED arrays when operating from 
the emergency driver. 

6.  Ensure there will be sufficient light output in the end application. Estimate the egress lighting 

illumination levels by doing the following:  

a.  Find the efficacy of the LED load. This can be given by the luminaire manufacture. This 

number will be given in lumens per watt (lm/w). It is the installer’s responsibility to 
validate the luminaire manufacturer’s efficacy data. This can be accomplished by direct 
measurement, by review of independent 3rd party test data (UL, ETL, etc.), accessing 
a public database of 3rd party data (such as Design Lights Consortium, 
www.designlights.org), or other comparable means.  

b.  Lumens can be calculated by multiplying the emergency mode power of the LED driver 

by the efficacy of the LED load. In many cases the actual lumen output in emergency 
mode will be greater than this calculation gives, however it will provide a good estimate 
for beginning the lighting design of the system.  

c.  Using the results of this calculation and industry standard lighting design tools, 

calculate the anticipated illumination levels in the path of egress. 

Lumens in 
Emergency Mode  

=  Fixture Efficacy 

*  Emergency Mode power of the product 

Lumens in 
Emergency Mode  

=  Fixture Efficacy 

Emergency Mode 
Output current 

*  LED Load V

f

 

(Lumens) 

=  __________ (lm/W) 

*  __________ (A) 

*  __________ (V) 

 

NOTE:

 This product has been designed to reliably interface with a wide selection of LED modules and 

is electrically compatible with every simple LED array that meets criteria 1 and 5 above. However, 
compatibility cannot be guaranteed with all current and future LED systems. Compatibility testing of 
the end-use system is suggested. Please contact the factory with any questions.  

NOTE:

 After installation, it will be necessary to measure the egress lighting illumination levels to 

ensure it complies with national, state, and local code requirements. 

Installation of this emergency LED driver will vary based on the luminaire type, however, generally 
follow these steps: 

STEP 1: INSTALLING EMERGENCY DRIVER 

  Disconnect AC power from the LED luminaire. 

  Mount the emergency LED driver along with the battery pack(s) by the mounting tabs. The 

luminaire’s installation instructions may provide guidance on the recommended mounting 
location.  

  Emergency driver & battery pack assembly (battery, wires & fuse) must be completely installed 

inside of a UL 1598 / CSA C22.2 no. 250 (Listed Luminaire) enclosure, or a UL 924 / CSA 
C22.2 no. 141 (Listed Emergency Lighting) enclosure.

 

No open holes should be left within an 

enclosure of wiring or electrical components. 

  The emergency driver and the battery pack(s), including fuses, as a system may be remote 

mounted from the luminaire, when installed within a UL 1598 / CSA C22.2 no. 250 (Listed 
Luminaire) enclosure, or a UL 924 / CSA C22.2 no. 141 (Listed Emergency Lighting) 
enclosure

 

 Please refer to the specification sheet for the maximum recommended remote 

mounting distance. Remote mount wiring must be in accordance with the National Electrical 
Code/Canadian Electrical Code and with local installation requirements.  