10
III.2010
DALI.Professional.Controller-4
Installation
Preparing the wiring
Wire.stripping.for.connecting.the.relays,.DALI.and.mains.cables.to.the.plug-in.termi-
nals:.10-12.mm.
10 - 12 mm
Relays
Depending.on.the.connection,.the.relays.function.as.break.contact,.make.contact.or.
make/break.contact:
Relays
Connection to K1, K2, K3, K4
Break.contact
Make.contact
Make/break.contact
Number of pushbuttons and sensor couplers
If.a.64.EVG.is.connected.to.a.DALI.circuit,.the.maximum.drive.current.available.in.this.
DALI.circuit.is.70.mA.
Specific.power.consumption.of.the.couplers:
•.
DALI.Professional.sensor.coupler:.5.mA
•.
DALI.Professional.pushbutton.coupler:.6.mA
à
.Connection.examples.of.a.DALI.circuit:
•.
14.Sensor.couplers
•.
10.Pushbutton.couplers.and.2.Sensor.couplers
If.more.couplers.are.required,.the.number.of.EVG.in.the.DALI.can.be.reduced..A.maxi-
mum.of.64.DALI.coupler.addresses.are.available.for.each.DALI.circuit..OSRAM.DALI.
couplers.can.also.be.deployed.across.all.circuits.
Pushbutton
Standard.commercial.pushbuttons.can.be.connected.to.the.pushbutton.couplers.or.
–.via.an.e:bus.DALI.gateway.–.capacitive.glass.touch.control.elements.and.touch-
screens.as.well..See.separate.operating.instructions.