OSCO Model T Instructions

Page 10

11-14-97

Control Wiring

Wire

Volts

Max Distance (ft)

Gauge

24V

250

14

350

12

For distances of more than 350 feet, a

long-distance interface is required.

USE COPPER WIRE ONLY

1.

Select your wire gauge from the top chart below.

2.

The distance shown in the chart is measured in feet from the operator to the power source. DO NOT
EXCEED THE MAXIMUM DISTANCE
.

3.

When large-gauge wire is used, a separate junction box (not supplied) may be needed for the operator
power connection.

4.

Select the gauge for control wiring from the bottom chart. For distances of more than 350 feet, a long-
distance interface is required.

5.

Wire run calculations are based on the National Electrical Code, Article 430, allowing 5 percent voltage
drop.

6.

Supply voltage must be within 10 percent of the operator rating under load conditions (not applicable for
208V).

7.

Connect power in accordance with local codes.

8.

The wire tables are based on standard copper wire.  Wire insulation must be suitable to the application.

Wiring Specifications

Power Wiring

Volts

Wire

& HP

Max Distance (ft)

Gauge

115V

281

12

448

10

713

8

1/2HP

1133

6

1802

4

Summary of Contents for Model T

Page 1: ...ety Installation and Service Manual OSCO requires the use of an electric edge or photoelectric control for pedestrian protection on all automatic or remotely controlled door operators OPERATOR SPECIAL...

Page 2: ...ion clutch Dependable roller chain drive Efficient V belt reduction Emergency disconnect for manual operation Double angle track 1 1 2 X 1 1 2 X 1 8 Door speed 0 8 0 9 feet per second 3 Headroom requi...

Page 3: ...hain sufficiently to remove any slack but once again do not overtighten as damage can result Using the 5 16 hardware provided attach the center rail supports to the rails Step 2 Header Bracket Positio...

Page 4: ...uld be brought into the operator with no smaller than No 12 wire For proper wire gauge refer to Wiring Specifications on Page 10 Electrical power must be ample and not taken from an overloaded line as...

Page 5: ...be wrong If the door closes when the OPEN button is pressed or vice versa any two of three motor leads must be reversed DO NOT REVERSE THE PUSHBUTTON LEADS TURN OFF POWER TO THE OPERATOR BEFORE MAKING...

Page 6: ...transformer C Check for a defective STOP button or loose connec tion in the stop circuit Door will not open from OPEN button but will close from CLOSE button A Make sure the open limit switch is not h...

Page 7: ...OSCO Model T Instructions Page 7 11 14 97...

Page 8: ...43 2100 801 Header Rail Support Bracket 22 2500 445 Motor 1 2 HP 115V 1 Phase Rail Pairs 1 1 2 x 1 1 2 42 2100 634 10 8 Long for 8 Door 2100 635 12 8 Long for 10 Door 2100 636 14 8 Long for 12 Door 21...

Page 9: ...OSCO Model T Instructions Page 9 11 14 97...

Page 10: ...ded for the operator power connection 4 Select the gauge for control wiring from the bottom chart For distances of more than 350 feet a long distance interface is required 5 Wire run calculations are...

Reviews: