OSB 2 SERIES Manual Download Page 19

OSB

 

Series 2 Oil-Fired Steam Boilers – 

Boiler Manual

Part Number 550-110-772/0816

19

Cleaning boiler flueways

  The boiler contains ceramic fiber and fiberglass 

materials. Use care when handling these materials 

per instructions on page 28 of this manual. This 

boiler contains ceramic fiber and fiberglass materials 

that have been identified as carcinogenic, or possibly 

carcinogenic,  to  humans).

Failure to comply could 

result in severe personal injury.

Figure 14  Cleaning boiler flueways — Thoroughly 

clean flueways between all pins at all 

angles. Start on top of boiler, finish from the 

bottom.

  Make  sure  all  electrical  connections  to  boiler  are 

turned off and wait until boiler is warm, not hot, 

before cleaning. Failure to do so will result in severe 

personal injury, death or substantial property damage.

1.  Remove jacket top panel.
2.  Remove flue collector hood, saving hardware for reassembly.

3.  Shut off oil valves. Arrange drip pans under the areas of oil 

piping that will be disconnected. Disconnect oil line at burner 

so that you can swing open the door completely.

4.  Line combustion chamber floor with newspaper to catch any 

soot that will be loosened in the cleaning process.

5.  Starting at the top of the boiler, use a wire flue brush to 

thoroughly clean between all pins at all angles. Be careful not 

to damage side walls of rear refractory.

6.  Move to the bottom of the flueways and clean up between the 

sections to reach pins left uncleaned in step #5.

7.  Once the flueways are cleaned, carefully remove the paper 

from the floor of the combustion chamber. Fold the paper to 

capture the refuse, seal in a plastic bag, and dispose.

8.  Verify sealing rope around flue area is intact. Visually check 

condition and position of insulation in combustion chamber 

floor,  and the refractories at the rear of boiler and in the burner 

mounting door. Replace any parts as necessary.

9.  Close burner mounting door and tighten nut securely. Place 

flue collector hood on top of boiler. Secure with hardware from 

step #2. Maintain a gas-tight seal to avoid possible flue gas 

leakage and carbon monoxide emissions, which can lead to 

severe personal injury or death.

10. Check breeching for sooting and clean if necessary. Install 

jacket top panel and breeching.

11. Reconnect oil line and all electrical connections.

  Wear a NIOSH -certified dust respirator (N95) while 

cleaning the boiler, per WARNING on page 28. Failure 

to comply could result in severe personal injury.

10 Service and maintenance 

continued

Reported problems

Inspect  any  problems  reported  by  owner  and  correct  before 

proceeding.

Boiler area

1.  Verify that boiler area is free of any combustible materials, 

gasoline and other flammable vapors and liquids.

2.  Verify that boiler area is free of any of the contaminants listed 

in Table 2 on page 5 of this manual. If any of these are present 

in the boiler intake air vicinity, they must be removed. If they 

cannot be removed, install combustion air piping to the boiler 

in accordance with national, provincial or local codes.

❏ 

Inspect . . . . . . . . . .

Piping

1.  Check the boiler interior piping and all system piping for signs 

of leaks.

2.  Repair any leaks before proceeding.

  Do not use petroleum-based cleaning or sealing 

compounds in boiler system. Severe damage to boiler 

will occur, resulting in substantial property damage.

  Eliminate  all  system  or  boiler  leaks.  Continual 

fresh makeup water will reduce boiler life. Minerals 

can build up in sections, reducing heat transfer, 

overheating cast iron, and causing section failure. 

Leaking  water  may  also  cause  severe  property 

damage.

Summary of Contents for 2 SERIES

Page 1: ...Installation and service certificate found on page 17 INSTALLER Read all instructions before installing Read page 2 first Follow all instructions in proper order to prevent personal injury or death Co...

Page 2: ...t has been under water Im mediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any burner control that has been under water Boiler wate...

Page 3: ...foundation is used Fire can result causing severe personal injury death or substantial property damage Foundation 1 Provide a solid brick or minimum 2 inch thick concrete foundation pad if any of the...

Page 4: ...st 140 sq in per 1 GPH input 1 sq in per 1000 Btu input of all fuel burning appliances plus requirements for any equipment that can pull air from room including clothes dryer and fireplace When outsid...

Page 5: ...level Shim legs if needed 3 Open burner mounting door Verify that chamber ceramic liner is securely in place on target wall chamber floor and burner door Verify door seal is intact and in place Close...

Page 6: ...cturer s instructions when excess draft needs to be relieved or to comply with applicable codes and regulations Use draft gauge to adjust proper opening 5 An induced draft fan for the chimney may be n...

Page 7: ...xtra strong or double strong pipe or connections DO NOT CAP PLUG OR OTHERWISE OBSTRUCT DISCHARGE PIPE OUTLET If discharge is piped upward a condensate drain must be provided in the elbow below the ver...

Page 8: ...arallel flow systems only Figure 7 Recommended piping OSB 6 piping for parallel flow systems only Float type low water cutoff If field installing a float type low water cutoff it must be piped only to...

Page 9: ...ler feed system with a condensate tank and feed pump You will have to install a low water cutoff pump control on the boiler to operate the pump See Low water cutoffs on page 20 and Figure 18 on page 2...

Page 10: ...ion or if state laws or local codes require certain water temperatures at hot water faucets take special precautions Install automatic mixing valve set according to those standards Use lowest practica...

Page 11: ...tandard equipment Burner wiring Burner harness incorporates a disconnect plug providing a convenient way to disconnect wiring when burner mounting door is opened See Figure 11 Wiring entrance The prob...

Page 12: ...12 Part Number 550 110 772 0816 OSB Series 2 Oil Fired Steam Boilers Boiler Manual NOTES this page left intentionally blank...

Page 13: ...OSB Series 2 Oil Fired Steam Boilers Boiler Manual Part Number 550 110 772 0816 13 6 Connect wiring continued Figure 12 Wiring diagram OSB boilers with low water cutoffs...

Page 14: ...threads Do not use Teflon tape as an oil pipe sealant It can cause valves to fail creating hazards Do not use compression fittings only flare fittings Failure to comply could result in severe persona...

Page 15: ...nual makeup water will reduce boiler life Minerals can build up in sections reducing heat transfer and causing cast iron to overheat resulting in section failure Failure to maintain recommended pH and...

Page 16: ...es Make sure burner goes off when control responds to low water condition Burner should re ignite when proper water level is restored 9 Test additional field installed controls If boiler has additiona...

Page 17: ...d _________________________________ Measured Btuh input ____________ Installer _______________________ ______________________________ __________________________________ company address phone _________...

Page 18: ...r a r e l i o b t a h t k c e h C d n a s r o p a v e l b a m m a l f r e h t o d n a e n i l o s a g s l a i r e t a m s d i u q i l 3 o t n o i t c u r t s b o y n a e v o m e r d n a r o f k c e h...

Page 19: ...s intact Visually check condition and position of insulation in combustion chamber floor and the refractories at the rear of boiler and in the burner mounting door Replace any parts as necessary 9 Clo...

Page 20: ...ype low water cutoff for proper operation Remove inspect and clean the low water cutoff at least annually before testing Refer to low water cutoff manufacturer s instructions in envelope assembly prov...

Page 21: ...e with this manual and the instructions on the relief valve tag Failure to comply will expose operator and others to severe personal injury or death Safety relief valves should be reinspected AT LEAST...

Page 22: ...22 Part Number 550 110 772 0816 OSB Series 2 Oil Fired Steam Boilers Boiler Manual 11 Replacement parts Figure 15 Boiler section assembly refractories collector hood and burner door assembly...

Page 23: ...back outlet includes rope and hardware for installation OSB 3 386 700 237WT OSB 4 386 700 238WT OSB 5 386 700 239WT OSB 6 386 700 240WT G Tie rod x 12 1 4 OSB 3 560 234 493WT Tie rod x 15 3 8 OSB 4 56...

Page 24: ...with two 2 3 8 x 1 2 black machine screws 2 Right and left side pieces are shipped as straight pieces Before installing bend about 90 at perforation as shown to form sides and back panels a Secure sid...

Page 25: ...Guage pressure 2 Dia Siphon NPT 180 Brass Nipple close NPT Tee NPT Elbow NPT Honeywell Inc Ametek PA404A1009 P505K 510 312 135WT 510 218 045WT 560 640 698WT 561 326 245WT 561 541 200WT 561 115 335WT...

Page 26: ...mber Supply tapping inches NPT Return tapping inches NPT A Supply riser spacing inches B Combustion chamber depth inches D Jacket depth inches OSB 3 2 1 2 2 13 1 2 16 7 8 OSB 4 2 1 2 2 16 5 8 20 OSB 5...

Page 27: ...45 174 546 131 83 9 7 8 x 8 7 15 14 2 0 015 OSB 6 1 75 210 658 158 83 7 7 8 x 8 7 15 16 0 015 Notes 1 MBH refers to thousands of Btu per hour 2 Base on 140 000 Btu per gallon of oil 3 Based on standar...

Page 28: ...it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fresh a...

Reviews: