13
03: Programmable outlets setting
Interface
Setting
Setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices
on battery mode.
04: LCD display direction setting
Interface
Setting
RAC: the LCD display is horizontal.
TOE: the LCD display is vertical.
00: Exit setting
Steps for setting programmable outlet
Step 1:
Before entering setting mode, the UPS should be in Stand-by mode
(off-charging)
and make sure the battery is connected.
The LCD
display is shown as right.
Step 2:
Press and hold the “Selection” button for 5 seconds to enter
Setting mode.
Step 3:
Press the “Up“ button (ON/MUTE) to switch to "02" of program list.
Then press “Enter“ button to enter value setting of parameter 2.
Press the “Up” button to change the value to “ENA” to enable the
programmable outlet function. Then press “Enter” button again to
confirm the setting.