WARNING
PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.
Electrical products can cause death or injury, or damage to property.
If in any doubt about the installation or
use of this product, consult a competent electrician.
INSTALLATION GUIDE
WARNING — THE INSTALLATION MUST BE CARRIED OUT BY
A QUALIFIED
ELECTRICIAN.
1.
DO NOT install near gas or electric heaters
2.
DO NOT use this LED Emergency Light other than its intended purpose
3. Equipment should be mounted in locations and heights where it will not be subjected to
tampering by unauthorized personnel
4.
LED Emergency Lights can only be installed by a qualified electrician
5.
This LED Emergency Light is f
or
indoor
use
ONLY
Instruction Manual
1-888-543-6473
1-888-541-6474
13376 Comber Way
Surrey BC V3W 5V9
[email protected]
www.ortechindustries.com
375 Admiral Blvd
Missis
s
auga
,
ON L5T 2N1
CAUTION
Application Notice
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, READ THE INSTRUCTIONS BELOW:
1. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition
2. In accordance with NFPA 101, your emergency lighting system MUST be tested monthly for a minimum of 30 seconds, annually for 90 minutes
3. Refer to your local codes for any additional requirements that may apply
4. Unused wires MUST be capped using enclosed wire nuts
5. Disconnect AC power before servicing
J-Box Mounting
1.
Feed fixture leads through the back plate and connect to AC power supply (See Fig.1).
For 120V, use black and white wires
and for 347V, use red and white wires
2. Attach back plate to J-Box and secure with screws
3. Complete the battery connection (see Fig.2)
4. Align snaps and push housing directly onto the back plate (see Fig.3). Apply continuous AC power and press "TEST" button to check light
LED Emergency Lights
MODEL
O
E-212
FLEXIBLE CONDUIT ONLY
Conduit
1.
Secure back plate to wall surface. Route wires through hole in conduit flange and make conduit connection.
For 120V, use black and white wires and for 347V, use red and white wires
2.
Complete the battery connection (see Fig.2)
3. Align snaps and push housing directly onto the back plate (see Fig.3).
Apply continuous AC power and press "TEST" button to check light
WARNING
Unused wires MUST be capped using enclosed wire nuts.
Fig.1 (J-Box)
Fig.2
Fig.3