8.    Serial Port 

This port allows connection and communication from the DB9 serial on the computer to the UPS 

unit. The UPS communicates its status to the software. 

9. 

Power On/Off Button 

Press the power Button to turn the UPS ON or OFF.

 

10.  Mute Button 

The audible alarm can be turned off/on by pressing this button for 3 seconds, and can also show 

page flipping by pressing this button for 1 second. 

11.  LCD Display 

The LCD will display the UPS status. 

 

 

DEFINITIONS FOR ILLUMINATED LCD INDICATORS 

 

LCD Indicators 

 

 

 

 

 

 

 

 

 

 

Line mode 

 

 

 

Bat-mode 

 

 

 

 
 

Alarm/Fault 

 

Sound disable 
(Press the mute 
key 3s to disable 
and enable the 
buzzer sound) 

 

 

 

Bat mode: battery capacity 
Line mode:   
1. Battery charging: cycle 
lighting 
2. Battery full charged: 
lighting 
3. Line mode without 
charger: battery capacity 

 

 
 
 

Load capacity 

 

Line mode & Bat mode 

 

Line mode 

Bat mode 

Initial 

 

 

2th 

 

 

3th 

 

 

 

TECHNICAL SPECIFICATIONS 

 

Model 

 

EP700R 

EP1000R 

EP1500R 

EP2000R 

Capacity    (VA) 

700VA 

1000VA 

1440VA 

1920VA 

Capacity    (Watts) 

420W 

600W 

900W 

1200W 

Input 

Input Voltage Range 

82V~148V 

Frequency Range 

60Hz +/- 5 Hz 

 

 

Output 

On Battery Output Voltage 

Sine Wave at 100-/-10% 

On Battery Output 
Frequency   

60Hz +/-1% 

Overload Protection 

Yes 

AVR Function 

Boost Function 

Yes                                                                                                                                                                                                                                                                                 

Buck Function 

Yes 

Physical

 

Total # of UPS 
Receptacles 

Nema 5-15R *8 

Maximum Dimensions   
(H x D x W) 

3.5 in x 16.9 in x 17.25 in 

Weight (lbs.) 

25 

29 

36 

37 

Battery

 

Sealed Maintenance Free 
Lead Acid Battery 

12Vdc 

24Vdc 

Typical Recharge Time 

8 Hours 

Warning Diagnostics 

Indicators 

LCD 

Communication

 

Communication port

 

HID USB/RS232 

SNMP Management 
Options 

External SNMP Adapter, External Temp Probe   

Environmental

 

Operating Temperature 

32

  to 122

  (0

  to 40

  )

 

Operating Relative 
Humidity 

0 to 90% NON-CONDENSING 

Management

 

Auto-Charger 

Yes 

Auto-Restart 

Yes 

 

TROUBLE SHOOTING

 

 

Problem 

Possible Causes 

Remedy 

    Abnormal

 

Mains normal but not   
Works in AC mode 

1. AC Input    missing 

1. Check AC input connection. 

2. Input Breaker is tripped 

2. Unplug the power cord of the UPS 

then press the circuit breaker knob. 

The UPS will not turn on

 

The on/off Button is designed 
to prevent damage by rapidly 
turning it off and on. 

Turn the UPS off.    Wait 10 seconds 
and then turn the UPS on.   

The unit is not connected 
to an AC outlet. 

The unit must be connected to a 
100-127V 50/60Hz outlet. 

The battery is worn out. 

Contact Technical Support. 

Mechanical problem. 

Outlets do not provide 
power to equipment 

Circuit breaker is tripped 
due to overload 

Turn the UPS off and unplug at least 
one piece connected equipment. 
Unplug the power cord of the UPS then 
press the circuit breaker knob. 

Batteries are discharged 

Allow the unit to recharge for at   
least 4 hours. 

Unit has been damaged 
by a surge or spike. 

Contact Technical Support. 

    Alarm 

Alarm code A06 

Battery capacity is low 

Alarm code A09 

Battery disconnected 

Alarm code A14 

Over load occurs. 

Alarm code A16 

EPO active 

Alarm code A18 

Over temperature 

      Fault

 

Fault code F06 

INV soft start fail 

Restart the UPS,

 

if the fault    is still, 

contact Technical Support 
 

Fault code F07 

INV volt high 

Fault code F08 

INV Volt low 

Fault code F09 

Output circuit short. 

Your attached equipment may have 
problems, please remove them and 
check again. 

Fault code F11 

Battery voltage is too high. 

1. Shut down the UPS 
2. Check the counts of Battery 
3.Check battery connector when 

use battery packages. 

Fault code F12 

Battery voltage is too low 

Fault code F13 

Battery    is

 

overcharge 

Fault code F14 

Over load occurs. 

Shut off non-essential equipment. 
If this solves the overload problem,   
the UPS will transfer to normal 
operation. 

Fault code F15 

load unbalance 

 

Fault code F18 

Fan has been damaged. 

Shut down the UPS, Replace the fan 

Fault code F19 

Over temperature 

1. Shut down the UPS. Restart the 
UPS to Check the fan for operation 
and if the ventilation hole has been 
covered. 
2. Contact Technical Support. 

      Other

 

Software is inactive 

The serial cable is not 
connected. 

Connect the serial cable to the UPS 
unit and an open serial port on the back 
of the computer. You must use the 
cable that came with the unit. 

The unit is not providing 
battery power. 

Shutdown your computer and turn the 
UPS off. Wait 10 seconds and turn the 
UPS back on. This should reset the 
unit. 

 

 