PT-Link-LON

®

 Technical Guide

                    

       

PT-Link Interface 

 

12

Implicit Addressing

Explicit and Implicit Addressing

Clients can address the PT-Link using explicit or implicit addressing. 
Clients using explicit addressing obtain their data transfer parameters 
directly from the PT-Link-LON confi guration fi le (confi g.csv). Implicit
addressing is used when a Network Management Tool such as LonMaker®
is used to connect a PT-Link-LON to other LonWorks nodes—the 
PT-Link-LON is assigned its data transfer (binding) parameters by the 
Network Management Tool. 

NOTE:

 

The PT-Link-LON is confi gured from the factory to use 
implicit addressing. 

Implicit Addressing

 — Network Manager assigns addresses for 

communication and ensures (via address tables in the devices) that 
communication connections are known.

Explicit Addressing

 — Device knows the address of the point in 

the remote device and communicates directly without the assistance of 
the Network Manager.

Implicit Addressing Commissioning Using

LonMaker

1.)  Ensure that the correct fi rmware and latest confi guration is 
 

loaded on the PT-Link-LON.

NOTE:

 

Each change in the PT-Link-LON requires re-commis-
sioning of the PT-Link-LON in LonMaker.

2.)  Ensure that the PT-Link-LON and the LonMaker machine 
 

are on the same network.

3.) 

Open

 the existing Network in LonMaker or create a new 

 Network.

4.) 

Click

 on 

Create New Network

 and follow the network 

 

wizard, making the following selections:

 

Network Interface:

 

Choose Network Attached

 

Management Mode:

 Choose Onnet unless you are

 working 

offl ine

 

Registered Plug-ins required

: None

5.)  Once Visio is open with the Network showing, drag a new 
 

device onto the drawing from the toolbox.

6.)  Follow the Device Network, making the following
 selections:

 

Enter Device Name

:

 Choose commission device

 

Specify Device Template

:

 Choose upload from device

 

Specify Device Channel

:

 Choose Auto Detect

 

Specify Device Properties

:

 Leave as is (Ping is optional)

 

Identify Device

:

 Choose service pin

 

Device Application Image

:

 Leave unchecked

 

Initial State

Leave as is

7.)  Press the service pin on the PT-Link-LON when asked to 
 

do so, and the PT-Link-LON will be commissioned.

8.)  Drag a new function block onto the drawing from the 
 

toolbox. Give the function block a name and ensure that it 

 

is allocated to the PT-Link-LON device.

9.)  Once the function block is on the drawing, you can drag 
 

input and output variables onto the function block. When 

 

you do this, LonMaker will show you the variables

 

avail able for binding. Click on the variables you require

 

(or use the select “all” option), and they will be

 

commissioned onto the function block.

10.) You are now ready to connect these variables to other
 

devices by dragging connections from the toolbox and

 

connecting the variables.

Summary of Contents for PT-Link-LON OE368-23-LON

Page 1: ...rioncontrols com VCM X Controller Code SS1026 Y200920 Version 2 0 and up VCM X Modular Controller Code SS1030 SS1034 VCM X WSHP Controller Code SS1032 SS1033 SA Controller Code Y200921 VCM Controller Code SS1016 Y200409 Y200616 Y200822 ...

Page 2: ...ws Vista 7 8 Running RUINET 9 Uploading Config csv to the PT Link 10 Downloading Config csv to the PT Link 11 Implicit and Explicit Addressing 12 Troubleshooting the PT Link Controller 14 PT Link Board LEDs 14 ProtoCessor Module LEDs 15 Troubleshooting Using RUINET 16 Verifying Proper Communications 16 Verifying Proper Values 16 Data Arrays 17 Table 2 VCM X Modular Data Array for Field Server 17 T...

Page 3: ... Data Sharing The PT Link LON interface provides the following data sharing ca pabilities Provides values from points on the Orion side of the gateway to LON devices as if the values were originating from LON objects Allows LON devices to modify point values on the Orion controller side of the PT Link LON by using standard LON write services Hardware Specifications Table 1 contains the hardware sp...

Page 4: ...the PT Link CD to your PC s Desktop You can also download the files from http orioncontrols com software new html under PT Link Setup Files 4 Connect your PT Link to your computer using an Ethernet connection Figures 3 4 5 Change your PCs IP Address Follow the directions that match your current operating system Windows NT XP Vista or 7 See directions on pages 7 8 6 Using RUINET edit the Config csv...

Page 5: ...PT Link Interface PT Link LON Technical Guide 5 Connection and Wiring Information Figure 2 PT Link LON Interface Wiring ...

Page 6: ...to the PT Link If connecting directly plug the other end of the Cable into the Ethernet port on the PT Link If connecting through an Ethernet Hub plug the other end of the PC cable into the hub and use a second CAT5 cable to connect the PT Link to the hub as well Power up the PT Link by plugging in the power cable The PT Link may take up to three minutes to power up completely Once the PT Link is ...

Page 7: ...Set up for Windows XP Vista and 7 In order for the PT Link to communicate properly it is imperative to set the IP address of both the PT Link as well as the computer to be within the same netmask You need to change the IP address on your computer The following instructions will explain how to configure the IP address for Microsoft Windows XP Vista and 7 operating systems IP Address Configuration 4...

Page 8: ...aring Center 4 From the shaded box in the left side of the window select Manage Network Connections Vista or Change adapter settings Windows 7 5 Right click on the Local Area Connection icon and select Properties for the drop down window 6 Choose Internet Protocol Version 4 TCP IPv4 by highlighting it and then click Properties The Internet Protocol Properties Window will appear Figure 8 7 Select t...

Page 9: ...reen LED displayed directly above and to the right of the Ethernet port This LED should be on if the 10 BaseT cable is good Secondly observe the red LED displayed directly above and to the left of the Ethernet port This LED should be solid while RUINET is running If the LEDs are lit as expected and RUINET still does not receive replies then the netmask is prob ably incorrect If this does not help ...

Page 10: ... Link contains an external interface file otherwise called an XIF file fserver xif The XIF file includes information such as SNVT names and LON network information This file can be uploaded for use with LON programming software When uploaded these files can be located in the same directory that the RUINETexecutable file is stored and run from Be sure when uploading that the correct file is specifi...

Page 11: ...restart RUINET It is possible to do multiple downloads to the PT Link before resetting it There will be a start up period where you will be unable to connect to the PT Link 14 From the RUINET Main Menu type A for the Data Array Overview The Data Array Overview Screen will display Figure 16 Changing the Config csv File Figure 16 Data Array Overview Screen 15 This screen Figure 16 will verify commun...

Page 12: ...en the existing Network in LonMaker or create a new Network 4 Click on Create New Network and follow the network wizard making the following selections Network Interface Choose Network Attached Management Mode Choose Onnet unless you are working offline Registered Plug ins required None 5 Once Visio is open with the Network showing drag a new device onto the drawing from the toolbox 6 Follow the D...

Page 13: ...onfiguration file by filling out the Title and System_Address fields of the PT Link LON parameters as follows Common Information Bridge System_Address Title 23 D48 S01 Wattmaster Explicit Lon v1 00d Figure 19 PT Link LON Domain and Subnet Setting The Title field must start with D followed by the domain_id in hexadecimal notation followed by S followed by the subnet_id in hexadecimal notation and e...

Page 14: ...each controller it is communicating with For example if you have 4 controllers on the loop connected to the PT Link LED 1 will blink 4 times If the amount of blinks does not match the number of controllers connected to the loop it indicates there is a com munications problem The best way to find out which board is not com municating is to go to each controller and look at its COMM LED The COMM LED...

Page 15: ...e LON LED will blink continuously until the PT Link has been commissioned Once commissioned the LON LED will remain off LA LED Once the unit is powered up the LA LED must be blinking constantly See Figure 21 If this LED is constantly on or off the Module is not working properly and needs to be replaced TX RX LEDs The TX and RX LEDs work together to indicate that communication is being established ...

Page 16: ...con stantly increasing move to the Error Screen by pressing the Space Bar 3 times to find out the cause of the errors Use the PgUp and PgDn keys to toggle between pages of the Error Screen Verifying Proper Values To verify that the correct values for each unit are being communicated to the PT Link move to the Data Array Overview Screen To get to the screen press A from the RUINET Main Menu See Fig...

Page 17: ...mp RaDmp RfPr 96 OaDwpt CoilTp SaTpStM PreHtSp OaCFM EtCFM SaCFM OACfmSt 104 OACfmRs OACfmStM MdCmp2 HdPr1 HdPr2 CdFan1 CdFan2 VCM X WSHP Tulsa Data Array For Field Server Offset 0 1 2 3 4 5 6 7 0 AppVer ClSt HtSt OaWtbl TpDmnd SpcTp SaTp RaTp 8 OaTp DuctPr OaRh UnitMode CtrlSts ClEnbl HtEnbl EcoEnbl 16 FanDly PofCfg CO2Cfg MdHt2Ins Rt2Ins OnRlys ExRlys12 ExRlys34 24 EcoPos VfdBwPos VfdExPos AlrmS...

Page 18: ...yPasDmp RaDmp RfPr 96 OaDwpt CoilTp SaTpStM PreHtSp OaCFM EtCFM SaCFM OACfmSt 104 OACfmRs OACfmStM MdCmp2 HdPr1 HdPr2 CdFan1 CdFan2 WaterTpA 112 A1LSPAlm A1LktAlm B1LSPAlm B1LktAlm LWT1Alm POWF1Alm ComMAlm Table 5 VCM X Data Array For Field Server VCM X Data Array For Field Server Offset 0 1 2 3 4 5 6 7 0 AppVer ClSt HtSt OaWtbl TpDmnd SpcTp SaTp RaTp 8 OaTp DuctPr OaRh UnitMode CtrlSts ClEnbl HtE...

Page 19: ...1 ExRly12 ExRly13 ExRly14 ExRly15 ExRly16 CO2St MinEcoSt 96 CO2Level ByPasDmp RaDmp RfPr OaDwpt CoilTp SaTpStM PreHtSp Table 7 VCM Data Array For Field Server Table 6 SA Controller Data Array For Field Server SA Controller Data Array For Field Server Offset 0 1 2 3 4 5 6 7 0 AppVer ClSt HtSt TpDmnd SpcTp SaTp DuctPr UnitMode 8 CtrlSts ClEnbl HtEnbl EcoEnbl FanDly MdHt2Ins Rt2Ins EcoPos 16 VfdBwPos...

Page 20: ...e in color This is a straight thru pin 1 to pin 1 cable not not 1 2 3 4 5 6 RJ 45 Connector as viewed from the bottom side 8 7 6 5 4 3 RJ 45 Connector as viewed from the bottom side Brown White White Brown Orange White White Blue Blue White White Orange White Orange Orange White White Green Blue White White Blue Green White Figure 25 RJ 45 8P8C Cable for WattMaster Cross Over Networking WattMaster...

Page 21: ...step may be skipped when application auto detects PT Link 3 From the RUINET Main Menu type A Data Array Overview 4 You should see 2 array items that are labeled wattmstr dump and wattmstr stats Ignore these 5 You should see 2 additional arrays for the controller connected Example DA_C162_I0 and DA_C162_I0b 5 1 The b at the end of the Data Array Name indicates that it is a mirror array You can igno...

Page 22: ...ockout Alarm A1LktAlm Binary Output Alarm that indicates Compressor A1 is locked out Compressor A2 Low Suction Pressure Alarm A2LSPAlm Binary Output Alarm that indicates Suction Pressure for Compressor A2 is below the Low Suction Pressure Cooling Heating Setpoint Compressor A2 Lockout Alarm A2LktAlm Binary Output Alarm that indicates Compressor A2 is locked out Compressor B1 Low Suction Pressure A...

Page 23: ...m A1LSPAlm Binary Output Alarm that indicates Suction Pressure for Circuit A is below the Low Suction Pressure Cooling Heating Setpoint Compressor A Lockout Alarm A1LktAlm Binary Output Alarm that indicates Circuit A Compressors are locked out Compressor B Low Suction Pressure Alarm B1LSPAlm Binary Output Alarm that indicates Suction Pressure for Circuit B is below the Low Suction Pressure Cooling...

Page 24: ... pressure sensor Return Air Temperature RaTp Analog Output Current value of the return temperature sensor SNVTs for the VCM X Controller Binary Output SNVTs are SNVT_lev_disc utput all other SNVTs are SNVT_count_inc_f Parameter Name Object Description Limits Indoor Humidity InRh Analog Output Current value of the indoor humidity sensor Space Temperature SpcTp Analog Output Current value of the spa...

Page 25: ... is the Supply Air Sensor then the cooling demand is always active 0 99 SNVTs for the VCM X Controller Binary Output SNVTs are SNVT_lev_disc all other SNVTs are SNVT_count_inc_f Parameter Name Object Description Limits Occupied Mode Enable Heating Setpoint OcpHtSt Analog Input If the control temperature drops one degree below this setpoint the control will activate the heating demand If the contro...

Page 26: ...ustable amount If you do not want Cooling to operate during the Unoccupied Mode use the default setting of 30 F for these setpoints 0 30 SNVTs for the VCM X Controller Binary Output SNVTs are SNVT_lev_disc all other SNVTs are SNVT_count_inc_f Parameter Name Object Description Limits Unoccupied Heating Offset UnHtOst Analog Input During the Unoccupied Mode of Operation this Setpoint spreads the Occ...

Page 27: ... of flow function has been configured REHEAT II Connected Rt2Ins Binary Output Status that indicates the MHGRV controllers is connected to the system SNVTs for the VCM X Controller Binary Output SNVTs are SNVT_lev_disc all other SNVTs are SNVT_count_inc_f Parameter Name Object Description Limits Mechanical Cooling Alarm MchClAlm Binary Output Compressor Relays are enabled but the Supply Air Temper...

Page 28: ...us of relay 2 On Board Relay 3 OnRly3 Binary Output Current status of relay 3 On Board Relay 4 OnRly4 Binary Output Current status of relay 4 On Board Relay 5 OnRly5 Binary Output Current status of relay 5 Expansion Relay 1 ExRly1 Binary Output Current status of relay 6 Expansion Relay 2 ExRly2 Binary Output Current status of relay 7 Expansion Relay 3 ExRly3 Binary Output Current status of relay 8...

Page 29: ...larm 2 HighControlTempAlarm 3 VcmxExternal Relays1 2Bits BIT STRING ExpansionBoard1Relay1 0 ExpansionBoard1Relay2 1 ExpansionBoard1Relay3 2 ExpansionBoard1Relay4 3 ExpansionBoard2Relay1 4 ExpansionBoard2Relay2 5 ExpansionBoard2Relay3 6 ExpansionBoard2Relay4 7 VcmxExternal Relays2 4Bits BIT STRING ExpansionBoard3Relay1 0 ExpansionBoard3Relay2 1 ExpansionBoard3Relay3 2 ExpansionBoard3Relay4 3 Expans...

Page 30: ...tware Version AppVer Analog Output Current version of the software in the unit Coil Temperature Setpoint CoilTpSt Analog Output Current Coil Temperature Setpoint Dewpoint Setpoint Mirror DptStM Analog Output Mirror of the DPtSt read only SNVTs for the SA Controller Binary Output SNVTs are SNVT_lev_disc all other SNVTs are SNVT_count_inc_f Parameter Name Object Description Indoor RH Setpoint Mirror...

Page 31: ...ClSt Analog Input Supply Air setpoint or Reset Source target temperature in Cooling Mode 40 80 SAT Reset Source Heating Setpoint SaHtSt Analog Input Supply Air setpoint or Reset Source target temperature in Heating Mode 40 200 SNVTs for the SA Controller Binary Output SNVTs are SNVT_lev_disc all other SNVTs are SNVT_count_inc_f Parameter Name Object Description Limits Supply Air Sensor Offset SaTp...

Page 32: ...nabled ClEnbl Binary Output Status that indicates mechanical cooling is enabled Economizer Enabled EcoEnbl Binary Output Status that indicates the economizer is enabled Fan Start Up Delay FanDly Binary Output Status that indicates the fan is commanded to run but it is in the start up delay mode Fan Proving Alarm PofAlm Binary Output Alarm that indicates a failure in the flow of the VFD blower Heat...

Page 33: ...l Failure CtrlTpCF Binary Output This alarm is activated if the control temperature does not get within 5 F to the occupied cooling setpoint in an hour in the cooling mode This alarm is not used in 100 outside air units or supply air control Control Temperature Heat Failure CtrlTpHF Binary Output This alarm is activated if the control temperature does not get within 5 F to the occupied heating set...

Page 34: ...rent value of the building pressure sensor Return Air CO2 Level CO2Level Analog Output Current value of the CO2 sensor Return Air Temperature RaTp Analog Output Current value of the re turn temperature sensor Space Temperature SpcTp Analog Output Current value of the space temperature sensor SNVTs for the VCM Controller Binary Output SNVTs are SNVT_lev_disc All other SNVTs are SNVT_count_inc_f Par...

Page 35: ...l will activate the cooling demand If the control temperature is the Supply Air Sensor then the cooling demand is always active 0 99 SNVTs for the VCM Controller Binary Output SNVTs are SNVT_lev_disc All other SNVTs are SNVT_count_inc_f Parameter Name Object Description Limits Occupied Mode Enable Heating Setpoint OcpHtSt Analog Input If the control tem perature drops one degree below this setpoin...

Page 36: ... Controller Binary Output SNVTs are SNVT_lev_disc All other SNVTs are SNVT_count_inc_f Parameter Name Object Description Limits Indoor Humidity Setpoint InRhSt Analog Input If the indoor humidity rises above this setpoint the unit will activate the Dehumidification Demand 0 100 Warm Up Setpoint WmupSt Analog Input In a VAV application upon entering the occupied mode the Warm up Demand will be acti...

Page 37: ...not shut the unit down SNVTs for the VCM Controller Binary Output SNVTs are SNVT_lev_disc All other SNVTs are SNVT_count_inc_f Parameter Name Object Description Limits Mechanical Heating Alarm MchHtAlm Binary Output Heating Mode has been initiated but the Supply Air Tempera ture has not risen 5 F w in a user adjustable time period This does not indicate heat stages are active and will not shut the...

Page 38: ...Expansion Relay 12 ExRly12 Binary Output Current status of relay 17 Expansion Relay 13 ExRly13 Binary Output Current status of relay 18 Expansion Relay 14 ExRly14 Binary Output Current status of relay 19 Expansion Relay 15 ExRly15 Binary Output Current status of relay 20 Expansion Relay 16 ExRly16 Binary Output Current status of relay 21 VCM PT Link LON Property Identifier The PT Link LON Link ame...

Page 39: ... ExpansionBoard3Relay3 2 ExpansionBoard3Relay4 3 ExpansionBoard4Relay1 4 ExpansionBoard4Relay2 5 ExpansionBoard4Relay3 6 ExpansionBoard4Relay4 7 VcmAlarmStatusBits BIT STRING Alarm Group1 0 Alarm Group2 1 Alarm Group3 2 VcmAlarmGroup1Bits BIT STRING SupplyTempSensorFailure 0 LostOutdoorTempSensorSignal 1 LostSpaceTempSensorSignal 2 VcmAlarmGroup2Bits BIT STRING MechanicalCoolingAlarm 0 MechanicalH...

Page 40: ...TLNKLON TGD 01N Printed in the USA September 2010 All rights reserved Copyright 2010 WattMaster Controls Inc 8500 NW River Park Drive Parkville MO 64152 Phone 816 505 1100 www orioncontrols com Fax 816 505 1101 ...

Reviews: