background image

Q I G

Quick Installation Guide

PRINTED ON RECYCLED PAPER

Q

uick

I

nstallation

G

uide

Q I G

The device can be connected to a serial device using a DB9 cable. The DB9
connector supports RS-232 / RS-422 / RS-485 operation modes. Please refer to
the following table for the pin assignments of the DB9 connector.

Wiring

The device has two sets of power inputs in the form of DC power jack and terminal.
The power input connectors are located on the top panel alongside the Ethernet
port. Follow the steps below to wire the power input on the terminal block.
Step 1: insert the negative / positive wires into the V-/V+ terminals, respectively.
Step 2: to keep the wires from pulling loose, use a small flat-blade screwdriver to
tighten the wire-clamp screws on the front of the terminal block connector.

Power inputs

Grounding and wire routing help limit the effects of noise due to electromagnetic
interference (EMI). Run the ground connection from the ground screws to the grounding
surface prior to connecting devices.

Grounding

Configurations

After installing the device, the green power LED should turn on. Please refer
to the following tablet for LED indication.

Environmental

-40 to 85 C (-40 to 185 F)

o

o

Storage Temperature

Operating Temperature

-40 to 85 C (-40 to 185 F)

o

o

5% to 95% Non-condensing

Operating Humidity

Regulatory Approvals

FCC Part 15, CISPR (EN55022) class A

EMI

EN61000-4-2 (ESD)

EN61000-4-3 (RS)

EN61000-4-4 (EFT)

EN61000-4-5 (Surge)

EN61000-4-6 (CS)

EN61000-4-8

EN61000-4-11

EMS

IEC60068-2-27

Shock

IEC60068-2-32

IEC60068-2-6

Vibration

EN60950-1

Safety

Free Fall

Warranty

5 years

IEC 61850-3, IEEE 1613

Power Automation

Oring Device Model

10/100 Base-T(X) Ports in RJ45

Auto MDI/MDIX

1

Physical Ports

Serial Ports

TxD, RxD, RTS, CTS, DTR, DSR, DCD, RI, GND

RS-232

RS-422

Power

Redundant Input power

Power consumption(Typ.)

Overload current protection

Reverse polarity protection

Present

Present on terminal block

Physical Characteristic

Enclosure

IP-30

Dimension (W x D x H)

72(W)x29.4(D)x123.4(H) mm (2.83x1.16x4.86 inch.)

Weight (g)

Stop Bits

1, 1.5, 2

Tx+, Tx-, Rx+, Rx, GND

294g

Data Bits

5, 6, 7, 8

Parity

odd, even, none, mark, space

RS-485 (4-wire)

RS-485 (2-wire)

Data+, Data-,GND

Flow Control

XON/XOFF, RTS/CTS, DTR/DSR

Network Protocol

Protocol

ICMP, IP, TCP, UDP, DHCP, BOOTP, DNS, SNMP V1/V2c, HTTPS, SMTP, DDNS, PPPoE, Modbus TCP

IDS-M311

Dual DC inputs. 12-48VDC on 3-pin terminal block and power jack

4 watts

Specifications

DB9 serial port

1 2 3

4 5

6 7 8 9

LED

Color

Status

Description

On

Power module 1 activated

Red

Blinking

DHCP servers do not respond properly

PW1/2

Green

On

Power is on and function normally

Green

On

Port running at 100Mbps

ETH

LNK/ACT

Amber

On

Port running at 10Mbps

Red

On

Receiving data

TX / RX

Green

On

Transmitting data

ORing Industrial Networking Corp.

Copyright© 2014 ORing

All rights reserved.

TEL: +886-2-2218-1066
FAX: +886-2-2218-1014

Website: www.oring-networking.com
E-mail: [email protected]

Pin #

RS

-

232

RS

-

422

RS

-

485

( 4 wire )

RS

-

485

( 2 wire )

1

DCD

RXD -

RXD -

2

RXD

RXD +

RXD +

3

TXD

TXD +

TXD +

DATA +

4

DTR

TXD -

TXD -

DATA -

5

GND

GND

GND

GND

6

DSR

7

RTS

8

CTS

9

RI

RS

-

232 mode act as DTE

Serial Baud Rate

110 bps to 115.2 Kbps

Connector

DB9 (male) x 1

Operation Mode

RS-232 / RS-422 / 4(2)-Wire RS-485. Which can be configured by Web interface

Tx+, Tx-, Rx+, Rx, GND

Version 1.0

IDS-M311

IDS-M311

Industrial Device Server

Device

Server

Device

Server

Reviews: