![Orbit Controls OC 7040A Owner'S Manual Download Page 7](http://html.mh-extra.com/html/orbit-controls/oc-7040a/oc-7040a_owners-manual_1648124007.webp)
3 TERMINALS
RS232
Request
Transmission
RS232
Continuous
Transmission
4 MENU
The key
MENU
opens the Menu. The required parameter will be confirmed with
ACK
. .
With
UP
or
DOWN
the parameters will be set.
The flashing digit - Cursor - can be positioned with
ACK
. The sign and the decimal point can be set after
the cursor is positioned outside the display range (none of the digit is flashing).
The key
UP
sets the decimal point, the key
DOWN
sets the sign. The key
SET
terminates the
programming and the display returns to the measuring mode.
KEY DISPLAY
FUNCTION
MENU PASS
Password selection from 20 stored combinations
ACK P 0200
Select with UP or DOWN
MENU
OrdEr
Decimal Point, Display Resolution
ACK
CCCC.dd
Select with UP or DOWN
MENU
Fn tArA
Tara function OFF, ONLY or ON.
ACK
ONLY
After pressing the key SET the display will be forced to zero
ON
The key SET pressed once forces the display to zero. When pressed for
second time, the display returns to the non-tare original signal value.
MENU
FiltEr
Setting of filter constant (averaging filter type)
ACK
OFF
Selection: OFF and 1, 2….99
MENU
Count
Counting of the last digit:
ACK 0
Dummy
Zero
1
The display increments 1, 2, 3….9, 0
2
The display increments 2, 4, 6…
5
The
display
increments
0,5,0,5…
MENU
dSP
Display refresh after selected number of measurements
ACK 1
Selection:
1,
2….50
MENU
SP 1
Set Point SP1
ACK
XXXXXX
Selection: -999999 to 999999. The relay is activated when the display
arrives at the SP1 or higher values
MENU
HSt 1
SP1 Hysterese
7
Summary of Contents for OC 7040A
Page 2: ...2 ...