background image

o

  HOLIDAYS. This is employed to choose a date period (day/month) on which 

the unit will be deactivated (switched off). This period will repeated year by 
year and begin to count from the 00:00:00 hours of the start day until the 
23:59:59 hours of the end day. 

-

  DEACT. No holiday adjustment. 

-

  EDIT. Configure the start day and the end day of the holiday lapse. 

 

o

 

KEYBOARD

. Menu to activate or deactivate the keyboard blocking protection 

to prevent unwanted access.

 

-

  BLOCK: NO. Protection is disabled. 

-

  BLOCK: YES. Protection is enabled. 

This protection is automatically activated 10 seconds after entering into 
MAIN screen mode. If keyboard is pressed, message KEYBOARD 
BLOCKED is displayed. At this point, in order to grant access and clears 
the protection, next keyboard sequence must be pressed: 

C

 

 

 

C

  

  

If a wrong sequence is pressed, message KEYBOARD ERROR will be 
displayed during several seconds. If correct sequence is pressed, 
NORMAL mode will be displayed and the device will be unprotected for 10 
seconds. During this lapse, access to MENU functions is granted by 
pressing 

 

o

 

COUNTER. 

Menu in which we will be able to know the ON-time (in hours) of 

each channel. 

 

-

  ERASE C1. It puts the hour counter of channel 1 to zero  

-

  ERASE C2. It puts the hour counter of channel 2 to zero 

  

o

 

INFRARED. 

For data downloading using the remote control, see the section 

DATA DOWNLOADING WITH THE REMOTE CONTROL). This option only 
works when the appliance is connected to the power mains. 

 

o

 

CONTRAST. 

Menu in which we can increase or reduce the display contrast.  

-

  MINIMUM, LOW, MEDIUM, HIGH, MAXIMUM  

When a key is pressed, the contrast will rise to the maximum level for three 
seconds. If no key has been pressed at the end of this time, the contrast will 
return to the previously selected value. 
The display is always at maximum contrast during programming. 
 

o

 

VERSION. 

This indicates the installed software version.  

 
If operations are programmed that coincide in time, it must be taken into account 
that some take priority over others. The priority order is as follows: 
OFF MODE 

Æ

 PERMANENT MODE 

Æ

 MANUAL 

Æ

PROG_01 

Æ

 PROG_02 

Æ

 

…. 

Æ

 PROG_70 

The data to be programmed always appear on screen in flashing mode.  

 
MANUAL OPERATION  

The status of the circuits may be temporarily activated or deactivated when in 
NORMAL mode by pressing the

 C1 and 

 C2 keys. The symbol 

 will appear 

on the screen until a programmed automatic operation takes place. 

 

 
Once changed, it is possible to return to NORMAL mode by repeatedly pressing 

C

.  

To verify channel status, the 

  key (INFO) should be pressed until the desired 

information appears. 
 

RESET  

Pressing the four keys at the same time until START AT appears on the display will 
delete all existing programming and the LANGUAGE MENU operating mode will be 
entered. The unit must be switched on in order to execute RESET. 
 

BATTERY CHANGE  

The unit has an operational 4-year backup using a replaceable lithium battery. 
Replacement of the battery is carried out by withdrawing the rotating button located 
on the right side of the unit. When the battery is exhausted and the device is not 
powered up “REPLACE BATTERY” is shown on the screen. 
NOTE: When changing the battery the unit programming is not lost, however the 
current time is lost. So we have to carry out the TIME SETTING again by means of 
the CLOCK menu.  
The battery cover is opened by rotating it counter-clockwise (marked by an arrow) 
with a coin or other flat object inserted into its slot, until the cover index coincides 
with the open position on the unit. After replacing the battery, the cover is inserted 
by placing it in the same position with the cover index coinciding with the open 
position on the unit and then turning it clockwise until the cover index coincides 
with the closed position on the unit. 
 

SWITCH THE UNIT OFF WHEN REPLACING THE BATTERY  

 
DATA-DOWNLOADING WITH THE REMOTE CONTROL 

Provided the DATA LOG + / 2+ is powered up, it can be controlled using an 
infrared remote control. Both the DATA and GPS SAT remote control models can 
be used with the DATA LOG + / 2+. 
 
This control can be used to read the equipment configuration, which will consist of 
the following parameters: 
 

-  Dates and times for summer and winter times changes 
-  Currently selected backlight intensity 
- Language 
- Programs 
- Keyboard 

blocking 

selection 

-  Holidays (start and end dates) 

 
This control can also be used to download all this configuration or just the current 
date and time. 
 
Infrared remote control access can be achieved in three different ways: 
1) In normal mode, the DATA LOG + / 2+ detects infrared communication from a 

control positioned in front and pressing MENU will cause the text “INFRARED 

PRESS MENU” to appear on the screen. Communications with the remote 
control can now take place. 

2) In normal mode, pressing the MENU key for more than three seconds will 

display the text “INFRARED WAITING”. Pressing MENU will provide access to 
this function. 

3) Pressing MENU in normal mode will enter menu selection. The 

 and 

 keys 

are used to select MENU ADJUSTMENTS and MENU is pressed again to enter 
this option. The 

 and 

 keys are used to select INFRARED ADJUSTMENTS 

and this option is entered by pressing MENU. Entering this menu will display  
“INFRARED WAITING” and communications are now available with the remote 
control. 

 
TECHNICAL SPECIFICATIONS: 

Voltage rating  

As indicated on the unit 

Tolerance  

± 10% 

Breaking power 

µ 2x16 (10) A / 250 V~    

Maximum recommended loads (N.O): 

  Incandescent lamps 

3000 W 

  Fluorescent lamps 

1200 VA

 

  Low-voltage halogen lamps 

2000 VA

 

  Halogen lamps (230 Vac) 

3000 W

 

  Low-consumption lamps (CFL) 

600 VA

 

  Low-consumption lamps (Downlights)   400 VA

 

  LED lamps 

600 VA

 

 
Self-consumption 

Maximum 4.5 VA Inductiv (1.8 W)  

Contact  

AgSnO

2

 switched  

Operational accuracy 

± 1 s/day at 23 ºC 

Variation of accuracy with temp.  

± 0.15 s / ºC / 24 h 

Running reserve  

4 years (without mains supply connection) 

Type of action 

1S, 1T, 1U 

Software class and structure 

Class A  

Memory slots 

70 

Nº of channels 

DATA LOG+: 1; DATA LOG 2+: 2 

Types of operation 

FIXED TIME: ON; OFF 
Pulse: from 1 to 59 seconds 
Cycle: from 1 minute to 99 hours, 59 
minutes 

Operating precision 

± 1 second  

Operating temperature  

-10 ºC to +45 ºC 

Transport and storage Temp 

-20 ºC to +60 ºC 

Contamination situation  

Protection degree 

IP 20 as per EN60529 

Protection class 

Class II in proper assembly 

Transient pulse voltage 

2.5 kV 

Ball test temperature 

+ 83 ºC for 21.2.5 

Keypad accesses cover  

Lockable 

Connection 

By means of needle post for maximum 
cable section of 4 mm² 

Battery 

½ AA – 3.6 V – 1000 mAh – Li/SOCi

2

 

Casing dimensions  

2 DIN modules (35 mm) 

 
 

DIMENSIONS 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

WARNING: 

This time switch incorporates a battery, the contents of which may be hazardous to 
the environment. The unit must not be discarded without taking the precaution to 
remove the battery and deposit it in a suitable container for recycling or returning it 
to the manufacturer. 
 
 
 
 
 
 
 
02/01.2013                                                                                          A016.17.56476 

 

ORBIS TECNOLOGÍA ELÉCTRICA S.A. 

Lérida, 

61 

  E-28020 

MADRID 

Tel.: + 34 91 567 22 77         Fax  + 34 91 571 40 06 

E-mail: 

[email protected]

 

http://www.orbis.es

 

35

88

60

65

Reviews: