2.2
Design
The wood burning stove series described in
these instructions are of "Design 1".
Wood burning stoves of this design have
self-closing firebox doors powered by a spring
mechanism and are approved exclusively for
use with the firebox closed. Wood burning
stoves of this design may be connected to
chimneys with multiple flues, provided the di-
mensions of the chimney permit this.
If the stove is connected to a chimney with
multiple flues, the closure springs of the fire-
box door must under no circumstances be re-
moved.
The firebox door must be able to close inde-
pendently once fuel has been added so that
any influence from the draught (feed pres-
sure) and associated risks and impairments
of other connected fireplaces can be avoided.
The design and condition of the chimney to
which the stove is to be connected plays a
key part in the fault-free operation of the wood
burning stove.
In all cases, have the suitability of the
chimney you intend to use checked by a
specialist.
3. Flue tube connection and
setup of the wood burning stove
3.1
Connection of the flue tube
Your wood burning stove can optionally be
connected upwards or to the rear. To connect
it to the chimney, a flue tube made from 2 mm-
thick sheet steel should be used.
All of the connections between the stove and
the chimney must be stable, solid, tight and
free from tension. Ensure that the flue tube
does not protrude into the clear cross-section
of the chimney.
We recommend using a liner.
The flue tube should run towards the chim-
ney in a slight upwards incline, but at the very
least horizontally.
In the case of wood burning stoves with the
option of top and rear connections, the flue
tube opening that is NOT used must be sealed
using the covering cap provided to prevent
smoke from escaping from it.
Caution!
If the feed pressure is too
low, or also too high,
malfunctions can occur.
If the differences compared
to the required feed pressure
(Point 4) are greater than
25%, then corresponding
measures must be carried
out on the chimney.
Note:
The connection pieces re-
quired for a connection on the
flue gas side are not included
in the scope of delivery.