Reviewing System Specifications
■
(CHECKLIST) Operate the air conditioning system for 48 hours to bring the room
temperature to the appropriate level.
■
(CHECKLIST) Clean and vacuum the area thoroughly in preparation for installation.
Reviewing System Specifications
■
“Physical Specifications” on page 96
■
“Installation and Service Area” on page 96
■
“Rack and Floor Cutout Dimensions” on page 97
Physical Specifications
Ensure that the installation site can properly accommodate the system by reviewing its physical
specifications and space requirements.
Parameter
Metric
English
Height
1998 mm
78.66 in.
Width with side panels
600 mm
23.62 in.
Depth (with doors)
1200 mm
47.24 in.
Depth (without doors)
1112 mm
43.78 in.
Minimum ceiling height
2300 mm
90 in.
Minimum space between top of cabinet and ceiling
914 mm
36 in.
Weight (full rack)
869 kg
1,916 lbs
Weight (half rack)
706 kg
1,556 lbs
Related Information
■
“Installation and Service Area” on page 96
■
“Rack and Floor Cutout Dimensions” on page 97
■
“Shipping Package Dimensions” on page 111
Installation and Service Area
Select an installation site that provides enough space to install and service the system.
96
Oracle SuperCluster T5-8 Owner's Guide • May 2016
Summary of Contents for SuperCluster T5-8
Page 1: ...Oracle SuperCluster T5 8 Owner s Guide Part No E40167 17 May 2016 ...
Page 2: ......
Page 11: ...Contents Index 353 11 ...
Page 12: ...12 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 14: ...14 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 116: ...116 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 204: ...204 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 228: ...228 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 244: ...244 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...