Preparing for Cooling
Rack
Approximate CFM
Exadata X5-2 Expansion Rack,
Extreme Flash, quarter rack
Maximum
Typical
572
401
Exadata X5-2 Expansion Rack, High
capacity, quarter rack
Maximum
Typical
533
373
Individual Extreme Flash storage
server
Maximum
Typical
94
66
Individual high capacity storage
server
Maximum
Typical
85
59
Related Information
■
“Environmental Requirements” on page 107
■
“Perforated Floor Tiles” on page 110
Perforated Floor Tiles
The default installation for the system assumes a slab floor, but if you install the server on a
raised floor, use perforated tiles in front of the rack to supply cold air to the system. Each tile
should support an airflow of approximately 400 CFM.
Perforated tiles can be arranged in any order in front of the rack, as long as cold air from the
tiles can flow into the rack.
The following is the recommended number of floor tiles:
Rack
Number of Tiles
Full rack
6
Half rack
4
Related Information
■
“Heat Dissipation and Airflow Requirements” on page 107
■
“Environmental Requirements” on page 107
■
“Rack and Floor Cutout Dimensions” on page 97
110
Oracle SuperCluster T5-8 Owner's Guide • May 2016
Summary of Contents for SuperCluster T5-8
Page 1: ...Oracle SuperCluster T5 8 Owner s Guide Part No E40167 17 May 2016 ...
Page 2: ......
Page 11: ...Contents Index 353 11 ...
Page 12: ...12 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 14: ...14 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 116: ...116 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 204: ...204 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 228: ...228 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 244: ...244 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...