Electrical Specifications
Description
U.S.
Metric
Maximum Width (from bezel front to rear protrusions)
17.52 in.
445 mm
Depth (chassis)
Maximum Depth (from bezel front to rear protrusions)
23.9 in.
25.2 in.
608 mm
640 mm
Weight (fully configured without PCIe cards)
†
47.3 lb
21.5 kg
Minimum service clearance (front)
36 in.
914.4 mm
Minimum service clearance (rear)
36 in.
914.4 mm
Minimum airflow clearance (front)
2 in.
50.8 mm
Minimum airflow clearance (rear)
3 in.
76.2 mm
†
Weight specifications vary based on internal options.
Related Information
■
“Electrical Specifications” on page 18
■
“Input Power Information” on page 19
■
“DC Power Source, Power Connection, and Grounding Requirements” on page 21
■
“Overcurrent Protection Requirements” on page 20
■
“Environmental Requirements” on page 22
■
“Acoustic Noise Emissions” on page 23
■
“Airflow Precautions” on page 24
Electrical Specifications
The values in this table are for the power supplies. Use the online power calculator to determine
the power consumption of a server with your configuration:
Parameter
AC
DC
Voltage (nominal)
100-127 VAC (800W max out)
200 to 240 VAC (1200W max out)
-48/-60 VDC (1200W max out)
40-47 VDC (900W max out)
Input current (maximum)
10A (100-127 VAC)
7A (200-240 VAC)
36A max @ -48 VDC bus
28A max @ -60 VDC bus
Frequency (nominal)
50/60 Hz
0 Hz
18
Netra SPARC S7-2 Server Installation Guide • January 2017
Summary of Contents for Netra SPARC S7-2
Page 1: ...Netra SPARC S7 2 Server Installation Guide Part No E73206 03 January 2017 ...
Page 2: ......
Page 8: ...8 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 10: ...10 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 26: ...26 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 60: ...60 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 96: ...96 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 102: ...102 Netra SPARC S7 2 Server Installation Guide January 2017 ...