OPW Installation, Operation and Maintenance Manual, Page 44                  Executive Order VR-401-C 

 

from the vantage point it will be viewed from in day- 
 
to-day operations to properly calibrate the gears. 
(See Figure 3.) 
 

 

Figure 3 

 

Step 11 

Place the lid gasket back into the groove, being 
careful not to damage it and keep it clean from 
debris. No sealant is necessary for this gasket. Add 

the cover and secure it tightly with the eight (8) 
bolts, using a crossing pattern, torque the bolts to 
15-20 ft-lbs.  

 
Annual Maintenance: 

Using a dip stick, measure the liquid level of the 
tank and check this value with the value displayed 
on the tank gauge.  The values should be within ±2 
inches of each other.  Recalibrate if necessary. 
Remove cover and visually inspect the internal 
parts for signs of wear, tangles in the spool, and 
corrosion.  Replace parts if necessary.   

 

 

9393 Princeton-Glendale Road, Cincinnati, Ohio 45011

 

1-800-422-2525 Domestically 

 

513-870-3315 Internationally

 

www.opw-fc.com

 

Copyright, 2009

 

OPW Fueling Components Inc., Cincinnati, OH

 

Printed in U.S.A. p/n H14912PA – 07/09

 