MD-30C version 3.2.000
6
Microphone desk and
voice alarm fireman's panel
ME-200C
3.
REAR VIEW
(1)
Ground connection.
(2)
Power supply fuse (0.5A).
(3)
24 VDC Power supply input (see section 5.1.).
(4)
Configuration DIP switches (see section 4).
DIP switch 1. RJ45 SHLD-GND LINK.
Allows separating the PIN
8 and the shield of the RJ45 connectors from the ME-200C
internal ground (GND).
DIP switches
2 and 3. BUS CAN END.
Configure DIP switches
2 and 3 to indicate the position on the CAN bus occupied by
the ME-200C (end element or intermediate element). If the
microphone desk is the final bus element, set these DIP
switches to ON position. If it is an intermediate element, set
them OFF.
DIP switches
5, 6, 7 and 8. CAN ADDRESS.
The microphone
desk communicates with the COMPACT system through a
CAN bus. Each ME-200C connected to the CAN bus must have
a different communication address. These DIP switches allow
you to assign this address.
(5)
INPUT and (6) OUTPUT connectors.
RJ45 Connectors. They are used to connect the equipment to
the COMPACT system. They transmit and receive the audio
and CAN data signals.
To connect them follow the section
The combination of the INPUT and OUTPUT connectors allow
the connection of several ME-200C microphone desks (up to
a maximum of 16) forming a BUS between elements. See
section
5.2.2. CAN Bus and audio connection between several
(7)
GONG volume.
(8)
Microphone volume.
Figure 2