INSTRUCTION MANUAL
A-225EN Version 1.1
1/1
A-225EN
At
WARNING:
Installation by qualified personnel only.
Speakers must be wired in parallel and connected to
the correct line terminals of amplifier.
Ensure that all speakers have the same polarity with
respect to each other.
Do not select another tapings if the speaker is in use.
No naked flame sources, such as lighted candles,
should be placed on the apparatus
.
CEILING SPEAKER
SPECIFICATIONS
Model
A-225EN
Loudspeaker
5”
Rated Power (RMS)
6 W
Power Taps 100V
6, 3 & 1,5 W
Impedance
1k6 , 3k3 & 6k6
Sensitivity
98,3 dB SPL at 1 W, 1 m IEC268-5
Sound Pressure
106 dB at 6 W, 1 m IEC268-5
Sensitivity EN54-24
74,9 dB SPL at 1 W /4 m
Frequency Response
57 ~ 24.000 Hz
Cutout Size
Ø 150 mm
Dimension (mm)
Ø 181,5 x 66 (depth)
Weight
0,6 kg
Finish
ABS, metallic grille
Colour
White RAL 9016
Mounting
Springs
Power selection
Transformer tabs
EN54 standard
EN 54-24:2008
Ref. No.: DOP_A225EN
ID-Code: A225EN
1438/CPR/0458
Loudspeaker for voice alarm systems for fire detection and fire alarm systems for buildings
Ceiling Loudspeaker, 6W, Type A
CE-Symbol according 93/68EWG
Other standards
VA special. In compliance with BS-5839, part 8.
Impedance
100 V
70 V
1k6
6 W
3 W
3k3
3 W
1,5 W
6k6 k
1,5 W
0,75 W
–
Common Common
INSTALLATION GUIDE