  |  Fire Protection  |  Data sheet No. 49103  |  Version 01-2016   

Specifications subject to change.

Manual call point DKM 3.3 – bus capable

Oppermann Regelgeräte GmbH

  |  Im Spitzhau 1  |  70771 Leinfelden-Echterdingen, Germany 

Phone +49 711 72723560  |  Fax +49 711 7280527  | [email protected] | www.oppermann-regelgeraete.de

Programming is only possible when the detector is disconnected from power.

 Programming is not possible if the loop is  

connected to power. Programming is also not possible during an alarm. Reset the alarm first.

Programming:

• 

Jack plug connector into programming tool (interface upper left) and the blue programming connector into the programming 
interface on the circuit board of the DKM.

• 

Switch on programming tool by pressing the left gray button. The address is read from the detector and shown in the display.

• 

Change address with the two gray buttons. Dots blink behind the figures while the address is being changed.

• 

Save address with the colored button. The blinking dots behind the figures vanish.

• 

Unplug detector and switch off programming tool.

Potential fault messages on programming tool:

bAt

Replace battery (battery service life: approx. 3,000 programming cycles)

E0

Incorrect programming attempt (Address > 127)

E1

DRM/DKM detector not found

E2

Detector not operational

E3

Incorrect sensor reply

E4

No detector found

E5

Read error

E6

Error while reading analog value (only DRM)

Programming with PG 3.3 programming tool

Socket for jack plug  

of programming cable

Battery compartment

9 V battery

• 

Store address

• 

Read analog value (for information)

• 

Switch on

• 

Adjust address in increments of 10

• 

Switch off

• 

Adjust address in increments of 1 

• 

Bus address display  
(1 – 127 possible, set 1 – 99 for STG)

• 

Fault indicator/analog value display  
(only on DRM)

The programming cable is only needed for push button alarm DKM 3.3

Summary of Contents for DKM 3.3

Page 1: ...anager can therefore see all connected detectors at a glance Important Note Please also note separate specification sheets for STG 1 2 The manual call point consists of the plastic housing and door It contains the circuit board with terminals trigger mechanism and push button The replaceable standardized thin glass pane in a lockable door protected by a standardized lock is a safeguard against uni...

Page 2: ... automatic fire detectors can be connected to a primary cable The test detector can be used on primary cables together with auto matic fire detectors It is connected at the electrical end of the primary cable max 1 test detector per primary cable The distance between non automatic fire detectors should be no more than 100 meters iaw DIN 14 675 and 80 meters iaw VdS Non automatic fire detectors sho...

Page 3: ... point DKM 3 3 bus capable Installation dimensions Space requirements toward the right to open the detector 60 mm 135 mm 37 mm 135 mm 17 mm 13 mm ca 35 mm Surface mounted installation remove circuit board first In wall installation 3 4 4 x 40 mm 2x S 5 2x 5 approx 35mm ...

Page 4: ...ry The assigned default address is 1 On request Oppermann can configure the detectors with custom BUS addresses indicate in your order The positioning of addressed DKMs in the ringbus is arbitrary A fault alarm is triggered if the same detector address is assigned twice on the ringbus If the detector address is changed the detector must be reregistered with the STG in service mode For connection t...

Page 5: ... Fire Protection Data sheet No 49103 Version 01 2016 5 6 Manual call point DKM 3 3 bus capable 1 3 2 1 2 4 7 mm 8 10 mm Wiring ...

Page 6: ...in the display Change address with the two gray buttons Dots blink behind the figures while the address is being changed Save address with the colored button The blinking dots behind the figures vanish Unplug detector and switch off programming tool Potential fault messages on programming tool bAt Replace battery battery service life approx 3 000 programming cycles E0 Incorrect programming attempt...

Reviews: