Onyx Controls ONX908PIT-V1-S1-F3/B Installation And Operation Instruction Manual Download Page 2

 

 

 

 

ONX908PIT-V1-S1-F3/B Modulating Digital Thermostat 

                                                       

Installation and operation instructions

 

The ONX908PIT-V1-S1-F3 modulating digital thermostats are designed to provide 

Proportional-Integral (PI) modulating control in 2-pipe or 4-pipe fan coil units, zoned commercial 

heating, Ventilating and various heating and cooling applications. 

This thermostat provides modulating analog 0-10V or 4-20mA control. Other available 

feature includes energy savings card key input, auto-detection of temperature sensor (remote 

sensor or internal sensor), and optional Celsius or Fahrenheit operation.   

 

SPECIFICATION: 

Input Voltage    …………………… 

24Vac, 50/60 Hz (Digital Thermostat) 

 

 

       24Vac-250Vac; 

50/60Hz 

(Fan) 

Output Voltage        ……………… 

Modulating output 4 to 20mA or 0-10VDC 

 

 

       On/Off 

output 

for 

fan 

5A 

250VAC 

Room temperature setting range………5

 to 35

 (41

 to 95

Accuracy……………………………. 

±

0.1

℉ or ±

0.2

 

Dimensions…………………………   115mm

×

90mm

×

28mm

 

Color………………………………..  White 

 

FEATURE: 

 

Large LCD display   

 

The screen displays the set temperature, the room temperature simultaneously 

 

Permanent user setting and program setting retention during power loss, 

 

Special energy saving mode-external input from window contact or hotel card-key overrides 

the temperature setting to installer defined heating and cooling temperatures 

 

0-10Vdc or 4-20mA heat and cool outputs 

 

3-speed fan control 

 

Fahrenheit or Celsius display capability

 

IMPORTANT SAFETY INFORMATION: 

 

Always turn off power at the main power source by unscrewing fuse or switching circuit 

breaker to the off position before installing, removing, cleaning, or servicing this thermostat. 

 

Read all of the information in this manual before installing this thermostat. 

 

Only a professional contractor should install this thermostat. 

 

All wiring must conform to local and national building and electrical codes and ordinances. 

 

Use this thermostat only as described in this manual. 

 

 

 

 

 

 

1

Summary of Contents for ONX908PIT-V1-S1-F3/B

Page 1: ......

Page 2: ...Accuracy 0 1 or 0 2 Dimensions 115mm 90mm 28mm Color White FEATURE Large LCD display The screen displays the set temperature the room temperature simultaneously Permanent user setting and program set...

Page 3: ...ximate Power Output of Modulation Output 8 Indicates the Portion of Modulating Output 9 Setting temperature 10 Shows temperature display in or 11 indicates when thermostat is in setback mode Energy sa...

Page 4: ...iate wiring schematic See figure 4 or figure 5 3 Push power base into wall 4 Using two mounting screws mount the power base to the wall Place a level against bottom of base adjust until level and then...

Page 5: ...ond heating output See configuration menu item 12 If it is selected as the sec heating output it will activate the second stage heating when the setting temperature is 1 plus P band value higher than...

Page 6: ...28 then the thermostat will control to 28 when the input signal activated the Energy Saving mode The energy saving mode input can be con ated either a short circuit default or open circuit signals ee...

Page 7: ...U I U 0 10 VAC output I 4 20 MA output Choose the control mode between 0 10VAC output to 4 20MA output 15 Press Power Button return to close 3 Select maximum temperature set point This feature provid...

Page 8: ...ortion ximum modulating output For example if you set the maximum 10 imum modulating output For example if you set the maximum F ure 5 of Output 10V or 20mA 0 50 100 H When the ambient temperatu 4 ig...

Page 9: ...output to control heating or cooling OF Only On Off output for heating control is available Terminal 7 and 8 output to control heating Terminal 12 and 13 is used as 0 10V or 4 20mA modulating output t...