Veris Pulse Output kWh Transducer (Single CT) Connection Instructions
Page 3 of 3
H22 and U30 Typical 208 or 480 VAC Three-Phase Three/Four-Wire Connection
Pulse Output kWh Transducer
(fuse pack not shown)
S-UCC-M006
Pulse Input Adapter
Black
Red
Yellow
Phase
Phase
Pulse-Rate Selection Switches and
Pulse Output Terminal Block (see details at below left)
Phase
*Note:
When using single CT model (T-VER-8051-300)
to monitor a
balanced
three-phase system, multiply
output pulse count by three for proper kWh indication.
White to (+)
Black to (-)
Pulse Output
Terminal Block Connection
1.00
12
3
4
5
6
ON
0.50
0.25
0.10
Pulse-Rate
Selection Switch Settings
0.1 kWh/Pulse*
0.25 kWh/Pulse*
0.50 kWh/Pulse*
1 kWh/Pulse*
1.00
12
3
4
5
6
ON
0.50
0.25
0.10
1.00
12
3
4
5
6
ON
0.50
0.25
0.10
1.00
12
3
4
5
6
ON
0.50
0.25
0.10
HOBO H22 or U30 Series Data Logger
(H22-001 shown)
Connect to
Smart Sensor port
Connect to pulse port
CABLE-2.5-STEREO
HOBO ZW Series Wireless Data Node
ZW Connection
(also refer to the appropriate CT wiring diagram in the H22/U30
connection section for your particular electrical power configuration)
Pulse Output kWh Transducer
(fuse pack not shown)
White to (+)
Black to (-)
Pulse Output
Terminal Block Connection
1.00
12
3
4
5
6
ON
0.50
0.25
0.10
Pulse-Rate
Selection Switch Settings
0.1 kWh/Pulse*
0.50 kWh/Pulse*
1 kWh/Pulse*
1.00
12
3
4
56
ON
0.50
0.25
0.10
1.00
12
3
4
5
6
ON
0.50
0.25
0.10
1.00
12
3
4
56
ON
0.50
0.25
0.10
0.25 kWh/Pulse*
*
Refer to asterisked note in the H22/U30
connection section for your particular
electrical power configuration