Veris Differential Pressure Transducer Connection Instructions
Page 3 of 3
ZW, U12, and UX120-006M Connection
Configuring the Data Logger for the Differential Pressure Transducer using HOBOware Software
HOBOware software provides configuration files for the transducers. The table below lists the recommended configuration values
that these files contain. For information on loading configuration files, refer to the software documentation.
Onset Part Nos.
Channel
Name
Warm-Up
Measurement
Type
Raw
Value 1
Raw
Value 2
Raw
Units
Scaled
Value 1
Scaled
Value 2
Scaled
Units
T-VER-PX3UL
Diff Pressure
20 sec
Current
4
20
mA
0
0.1 (or 0.25,
0.5, 1, 2.5,
5, or 10)
in WC
Voltage
0
5 (or 10)
V
Velocity
20 sec
Current
4
20
mA
0
500, 1000,
2000, 3000,
4000, 5000,
6000, or
7000
ft/min
Voltage
0
5 (or 10)
V
Notes:
•
Excitation power provided by the FlexSmart Analog Module (Onset Part No. S-FS-CVIA) with H22; by the Analog
Sensor Port/Module with U30 and RX3000; and by power adapter (Onset Part No. AC-SENS-1) with ZW, U12, or
UX120-006M.
•
Both differential pressure transducer models have switch-selectable ranges and scales, as listed.
HOBO ZW Series Wireless Data Node; U12 or
UX120-006M Logger (ZW shown)