Veris Differential Pressure Transducer Connection Instructions
For use with HOBO
®
H22, U12, U30, UX120-006M, and RX3000 data loggers and HOBO ZW data nodes
© 2018 Onset Computer Corporation.
All rights reserved. Onset, HOBO, HOBOware, and HOBOlink are registered trademarks and FlexSmart is a trademark of Onset
Computer Corporation. Other products and brand names may be trademarks or registered trademarks of their respective owners.
22415-B
Applies to these Veris Differential Pressure Transducers:
Onset Part No.
Air Pressure Range
Output
Veris Part No.
T-VER-PX3UL
0-10” WC
4-20mA (or 0-5V/0-10V) representing 0 to 10” WC
PX3ULX05
This document provides instructions on connecting the Veris Differential Pressure
Transducer listed above to each of the following:
•
FlexSmart
™
Analog Module used with HOBO H22 series data loggers
•
Analog Sensor Port/Module used with HOBO U30 and RX3000 series data
loggers
•
Voltage adapter used with the U12 and UX120-006M data loggers and ZW series
data nodes
It also lists configuration values used by HOBOware
®
software to configure the logger for
each transducer.
Note:
For information on connecting the differential pressure transducer
to the pressure source, and other transducer details, refer to the documentation provided
by Veris.
Required
•
Selected Veris Differential Pressure Transducer
•
HOBO H22, U12, U30, UX120-006M, or RX3000 data logger, or HOBO ZW data node
•
FlexSmart Analog Module, Onset Part No: S-FS-CVIA (for H22 series); Analog Sensor Port/Module option (for U30 and
RX3000 series); voltage adapter, Onset Part No. CABLE-ADAP5 or CABLE-ADAP10 (for U12, UX120-006M, or ZW
series)
•
HOBOware software, version 2.2.1 or higher (2.4.0 or higher for U30 series; 3.6 or higher for UX120-006M);
HOBOware Pro 3.0 or higher for ZW series
•
HOBOlink (for RX3000 series data loggers)
•
Customer-supplied length of 18 AWG, shielded, multi-conductor cable
Connecting the Differential Pressure Transducer to the Analog Module or Port
Veris Differential Pressure Transducer