System-10 Dual Network Interface Installation Guide
Page 10
Powered Pulse:
This type of output refers to a pulse which has an associated voltage with it (see Fig. 2). Set the selector
switch, S1 to Pwrd Pulse. The allowable voltage range is 5-24 VDC. The input impedance is set at
the factory to be 11 KOHM via the impedance selector jumper (J1, see Fig. 1). A lower impedance,
3 KOHM can be selected if required by the instrument providing the pulse output. Consult the
instrument manufacturer or ONICON if you are uncertain as to the proper jumper selection.
Fig. 2
Open Collector (Sourcing):
This type of output refers to an open Collector Switch configured for a sourcing function (see Fig. 3).
Set the selector switch, S1 to SRC. The switch must be rated for at least 20 mA at 20 VDC.
Fig. 3
Di3 In (+)
Di3 In (-)
Di3 In (+)
Di3 In (-)
ONICON
BTU Meter
ONICON
BTU Meter